background image

 

R000226 BP1 Automation 

v.0.1 03/21 

5  

INSTALLATION AND WIRING 

 
This section describes the installation of a complete BP1 system, or an IMC3-J 
automation that has been retrofitted with a BP1 control board. For instructions on 
conversion of an IMC3-J automation to a BP1, see Appendix A.1.  
 

5.1 Installation, BP1 Complete System p/n A000393 

  Connect the control cables as described in Sec. 5.2.  

  If the fire alarm panel provides a contact closure during an alarm, configure the Fire 

Alarm input jumpers at JP2 to the “Contact” position. If the fire panel provides 
voltage during an alarm, leave the two jumpers in the factory default “Volts” position. 
Note: Both jumpers must be in the same position, either Contact or Volts (This 
jumper setting has no effect when the BP1 board is used as a retrofit in an IMC3-J 
automation – this function is controlled on the Fire Relay PCB). 

  If you wish the BP1 to only 

flash

 the fire alarm LED on the front panel rather than 

hold it, change jumper JP1 to the “Pulse” setting. If you change it to Pulse, there 
will not be a continuous indication of the alarm condition on the front panel LED. 
Note: This jumper setting only affects the behavior of the LED on the front panel. 

  Install the unit in an available rack space.  

  Connect the power supply to an AC receptacle.  

  Configure the projector as described in Sec. 6. 

 

5.2 Attaching Control Cables 

Connect four cables as described below. See Figure 5-1 for images. 

  Connect an 8-conductor cable from the BP1 J1 to the Alchemy ICMP-X GPI1-4 

(this cable delivers the Fire Alarm output signals back to the projector). 

  Connect an 8-conductor cable from the BP1 J2 to the Alchemy ICMP-X GPO5-8. 

Note: This cable controls the Screen Lights only. If there are no screen lights at this 
particular theater, this cable is optional. 

  Connect an 8-conductor cable from the BP1 J3 to the Alchemy ICMP-X GPO1-4 

(this cable carries the dimmer control signals from the projector to the BP1). 

  Connect an 8-conductor cable from the BP1 J4 to the Projector Cinema Controller 

Board (CCB) GPO5-8 (this cable carries the Masking signals and XL-Mover signals 
from the projector to the BP1). 

Note: Depending on the projector model this last cable may have to be broken out at 
the projector end for connection to the 37-pin “General Purpose I/O” connector as 
shown in Figure 5-1. See Section 5.3 for more detailed information on making the 
breakout connector. If a breakout cable isn’t required proceed to Section 6. 

 

 

Содержание A000392

Страница 1: ...R INSTALLATION OPERATION AND MAINTENANCE OF BP1 Automation Part numbers A000392 A000393 Manual Version 0 1 MOVING iMAGE TECHNOLOGIES LLC 17760 Newhope St Fountain Valley CA Telephone 714 751 7998 Fax...

Страница 2: ...represent a commitment on the part of Moving Image Technologies hereinafter referred to as MIT MIT does not assume responsibility for errors that may appear in this document MIT or its subsidiaries de...

Страница 3: ...he various pieces of equipment in the cinema auditorium such as dimmer and masking control The BP1 system is built on 19 wide 1 RU steel chassis The main circuit board incorporates detection logic tha...

Страница 4: ...P P P P P P P P P A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A P P F F F F P P F F F F P P F F F F P P F F F F P P F F F F P P A A A A P P A A A A P P F F F F P P F F F F P...

Страница 5: ...cabling may be required Or you may assign different functionality to the connectors than the default functions listed below if desired All connections between the BP1 and projector use 8 pin RJ 45 con...

Страница 6: ...J3 7 NC J3 8 Common J4 PROJ GPO5 8 J4 1 Masking Flat J4 2 Common J4 3 Masking Scope J4 4 Common J4 5 XL Mover 2D J4 6 Common J4 7 XL Mover 3D J4 8 Common TB2 Fire Alarm legacy used in retrofit versio...

Страница 7: ...tput a voltage to the projector of 9VDC current limited by a resistance of 700 ohms J1 1 Fire Alarm Mode Active J1 2 Fire Alarm Mode Active J1 3 Fire Alarm Cancel Reset J1 4 Fire Alarm Cancel Reset J1...

Страница 8: ...ipping damage If damage is found notify the freight company immediately The contents of the carton contains the following items One A000393 BP1 complete system plus interconnect cables standalone One...

Страница 9: ...s jumper setting only affects the behavior of the LED on the front panel Install the unit in an available rack space Connect the power supply to an AC receptacle Configure the projector as described i...

Страница 10: ...R000226 BP1 Automation 10 v 0 1 03 21 Figure 5 1...

Страница 11: ...r Breakout dp B085H8MQ35 ref sr_1_1_sspa The connections should be made as shown in Figure 5 2 DB37 Pin RJ45 Pin RJ45 Color 13 1 32 2 14 3 33 4 15 5 34 6 16 7 35 8 Figure 5 2 Some IMB manufacturers e...

Страница 12: ...MP X s web UI Parts and Tools Needed A complete BP1 automation system or an IMC3 J automation retrofitted with the BP1 JNIOR replacement board as described in the Appendix Three cat 5e or cat 6 Ethern...

Страница 13: ...igure 6 1 Configuring the ICMP X GPO Cues 3 Configure the GPIO cues that output from the ICMP X and input to the BP1 First create a new cue group for ease of access In this example it has been called...

Страница 14: ...e cues click Add You will now create the five GPO cues that the BP1 can accept Dimmer Mid Dimmer Down Dimmer Up Screen Lights On Screen Lights Off Figure 6 3 Adding New Cues 5 Once you have added the...

Страница 15: ...Up GPO 4 is not used by the BP1 5 Screen Lights On 6 Screen Lights Off GPO 7 and 8 are not used by the BP1 Figure 6 5 Configuring the ICMP X GPI Cues 6 Next create the two GPI cues that the ICMP X rec...

Страница 16: ...of the fire alarm inputs to the BP1 If the fire alarm input to the BP1 mode is set to PULSE then the GPI to the ICMP X should be configured as On Input X Up If the fire alarm input is set to HOLD the...

Страница 17: ...8 The next step is to configure what the ICMP X will actually do in response to receiving the GPI cue This is done by adding commands to the cue in the same way that GPO output commands were added to...

Страница 18: ...eceived on GPI 1 fire alarm active will cause DCP playback to be paused and then half a second later the projector s dowser to close How you select and configure these commands will depend on how you...

Страница 19: ...s preset macros that require their use The four projector GPO functions that the BP1 uses to trigger external devices are shown in Figure 6 13 GPO Output Function GPI 1 through 4 are not used by the B...

Страница 20: ...he macro after adding the new command 13 Given that the XL Mover takes about 10 seconds to move the 3D filter into position and we don t want anything to be projected until this is complete we will no...

Страница 21: ...r to save when done Using the cues in an ICMP X Show Playlist 14 We can now add the new automation cues that have been created to operate the BP1 into our show playlists SPLs In the ICMP X s web UI We...

Страница 22: ...reated in the projector s Barco Communicator app are now available for use in SPLs To add a cue to your playlist drag it and drop it By clicking on the timecode you can also adjust the time delay afte...

Страница 23: ...ting If the jumper is placed in the HOLD position the fire alarm input will be latched and will hold that state indefinitely until it s released with the button on the front panel If the jumper is pla...

Страница 24: ...mation tray back into place and secure it 13 Plug in the power supply This completes the installation procedure Figure A 1 shows the IMC3 chassis after the installation of the BP1 Control PCB Fig A 1...

Страница 25: ...MODELS AND PART NUMBERS A000392 001 BP1 Retrofit version Control PCB and cables only A000393 001 BP1 Standalone version complete REPLACEMENT PARTS LIST B000630 001 BP1 Control PCB only B000631 001 BP1...

Страница 26: ...ported in writing to Moving Image Technologies not later than seven 7 days after the expiration of the twelve month warranty period c which are returned to Moving Image Technologies promptly after dis...

Страница 27: ...of this document When contacting MiT be prepared to provide Model and serial number Part name and part number as shown in this manual Original Purchase order number The purchase order number is essen...

Отзывы: