R000226 BP1 Automation
7
v.0.1 03/21
TB4 Fire Alarm & DC Power Input (used in standalone version, not used in retrofit version)
TB4-1
Fire Alarm Panel 1 (no polarity)
TB4-2
Fire Alarm Panel 2 (no polarity)
TB4-3
+12V
TB4-4
12V Return
Outputs
Note: all outputs are dry contact relay closures when activated, except as described below. All
outputs are pulsed for ~0.5 sec, then return to the quiescent, inactive state.
J1 ICMPX GPI1-4
Note: this output jack is unique in that the two signals output a voltage to the projector of ~9VDC,
current-limited by a resistance of ~700 ohms.
J1-1
Fire Alarm Mode Active, +
J1-2
Fire Alarm Mode Active, -
J1-3
Fire Alarm Cancel/Reset, +
J1-4
Fire Alarm Cancel/Reset, -
J1-5&6
NC
J1-7&8
NC
J5 MiT XL Mover Control
J5-1
2D
J5-2
3D
J5-3-7
NC
J5-8
Common
Note: The J5 connector pinout matches the pinout of the standard XL Mover control input and the
control cable delivered with the XL Mover. If the XL Mover control cable has been modified in any
way, it must be restored to the factory configuration or replaced with a new one, p/n B000573-001.
See Figure 3-2 for wiring.
Figure 3-2
TB5 Screen Lights
TB5-1&2
Screen Lights On
TB5-3&4
Screen Lights Off