R000226 BP1 Automation
16
v.0.1 03/21
7. Next define the GPI behavior that triggers the action.
Figure 6-7
The choice of up or down will depend on the configuration of the fire alarm inputs to the
BP1. If the fire alarm input (to the BP1) mode is set to PULSE, then the GPI to the ICMP-
X should be configured as “On Input X Up.” If the fire alarm input is set to HOLD, then the
GPI to the ICMP-X should be “On Input 1 Down.” You should also ensure that the mode
jumper is set correctly on the BP1 board, as shown in Figure 6-8.
Figure 6-8