Leak Detection is a factory-installed option that enables the unit to 
detect a leak in the nozzle circuit.

• Determine whether leak detection is installed on the unit by 

navigating to the DATA Menu and cycling  through the variables 
by pressing the green 

button .  If you see values labeled FL, 

TL, AFR and TOL, then the option is installed.

• Adjust the tolerance for leak detection to be either more or less 

forgiving in recognizing a problem.

• The default tolerance is 75%  That is, Gen 1.3 will not detect 

and annunciate a leak until the Actual Volume is more than 
175% of the Calculated Volume. 

• Setting the TOL value in the DATA Menu to a higher number 

makes the unit more tolerant of a leak.  Setting the TOL value 
lower makes the unit more sensitive.  100% is the allowed 
maximum.

• To change the value, go to the DATA Menu, TOL. Press 

Green 

button for 5 seconds, then use the arrow keys to 

adjust the value.

• Disable leak detection by 1) unplugging the unit from the 

electrical socket, 2) unplugging the 6 pin connector on the back of 
the controller, and 3) plugging the unit back into the electrical 
socket.

• NOTE: Leak Detection may not function properly on systems with 

less than 20 nozzles and/or mist durations less than 30 seconds.

Optional Leak Detection

Section 3

Setting Up the Unit

• Clear area
• Pres MIST button on transmitter
• Unit will MIST.

If Remote Agitation (RAG) is set to a 
value greater than 0, system with 
Agitate (AGT) prior to MIST.

12. Test by Activating 

Remote Mist

• Close lid
• Fit elastic at waterproof cover 

bottom under lip along edge of drum.

13. Cover Unit

Section 3

Setting Up the Unit

• Add insecticide through large bung 

with a funnel.

• Top off drum with water.  Maintain 

air gap of 6” between hose and fluid 
level.

• Do not overfill.  Stop filling when 

level is 4” from the top.

• MAINTENANCE Menu, LEVEL
• Press green 

button and use 

arrows to set level to full (8 bars)

10. Add insecticide, top 

off drum, Reset 
LEVEL to full

• MAINTENANCE Menu, scroll to INS
• Depress Green 

button 5 seconds

• Unit will mist for 5 minutes or until 

stopped.

• Confirm no leaks in nozzle circuit.
• Confirm pump pressure is 240 psi.  

If not, insert flat head screwdriver 
into port on back left and adjust 
pump bypass until pressure is 240 
psi.  Reinsert plastic plug into port.

• If zone valve installed, repeat using 

INS2. (Set pressure so that it does 
not exceed 240 psi in either zone.)

9.

Run Inspection Cycle

• With the display showing day, time 

and level, press Green 

button to 

position the 

at top of display 

pointing to the active System Mode:

• OFF - daily agitation cycle only
• REM or ON – remote and manual, 

but no programmed mist

• AUTO Everyday – program runs 

daily.  This is the usual mode.

• AUTO Custom – program runs on 

days configured in CUSTOM PGM

11. Set System Mode

Содержание Drum-Based Misting Unit Gen 1.3

Страница 1: ...MistAway Drum Based Misting Unit Gen 1 3 Operations Manual Copyright 2013 by MistAway Systems Inc...

Страница 2: ...ds The unit will also mist in response to a signal from a handheld remote transmitter for a duration programmed by the user Base Functionality Optional Equipment and Functionality MistAway Drum Based...

Страница 3: ...lling Insecticide label and dilution statement should be securely attached to the unit reservoir in a weatherproof pouch Strictly follow label instructions regarding storage and disposal of insecticid...

Страница 4: ...or empowered to give any other warranty or to assume any other liability on behalf of MSI Warranty Conditions This warranty is extended only to the original Purchaser and is not transferable A purchas...

Страница 5: ...red for units supplied with Agitating valves Pressing Green button will cycle through each of four System Modes The at the top of the display points to the active System Mode 1 OFF If equipped with ag...

Страница 6: ...Menu LEVEL Press green button and use arrows to set level to full 8 bars Section 3 Setting Up the Unit Set Day and Time note AM and PM Exit by pressing Menu button a Set Day and Time SET UP Menu AGT S...

Страница 7: ...etting Up the Unit Clear area Pres MIST button on transmitter Unit will MIST If Remote Agitation RAG is set to a value greater than 0 system with Agitate AGT prior to MIST 12 Test by Activating Remote...

Страница 8: ...REMOTE MIST if the Remote Agitation Duration SET UP RAG is set to a value greater than 0 seconds NOTE on pre 2012 systems agitation duration before a remote mist is fixed at 15 seconds If a Zone Kit i...

Страница 9: ...xing guidance Conventional Insecticide Formulations Exempt or Green Insecticide Formulations Section 5 Managing the Insecticide It is important to note that there are differences of opinion among mist...

Страница 10: ...ists this virtual volume is reduced by a calculated estimate of the volume of dilute insecticide that was misted through the nozzle circuit When the virtual volume equals 0 EMP Empty is displayed on t...

Страница 11: ...ouling the intake filter or nozzle circuit Clean filter on pump intake line Remove filter from intake line Use wire brush and hose to remove debris 1 Flush pump and agitation valve if equipped and noz...

Страница 12: ...circuit to drain and cause ERR3 to be displayed That is the error condition does not occur while the user is on site troubleshooting the issue Leak Detection ERR3 MIST volume greater than expected Sec...

Страница 13: ...trical power is restored to the unit the digital controller will return into the same mode the unit was operating in prior to the power being turned off For example if the unit was in AUTO EVERYDAY mo...

Страница 14: ...n agitating valve a pressure gauge is mounted into the plastic housing Pump Intake Line and Filter Pump intake positioned near bottom of drum Filter ensures debris is not drawn into pump and nozzle ci...

Страница 15: ...on cycle prior to a remote mist cycle RAG not available on pre 2012 systems TNK Set reservoir size in gallons 5 995 SEN Turn optional wind sensor ON or OFF WND Set max wind speed above which wind sens...

Страница 16: ...s quickly INS Unit is in Inspection Mode and will mist for 5 minutes or until stopped MST Unit is misting NOZ00 Unit stopped operating because the number of nozzles is set to 0 Clear by pressing Red S...

Отзывы: