Leak Detection is a factory-installed option that enables the unit to
detect a leak in the nozzle circuit.
• Determine whether leak detection is installed on the unit by
navigating to the DATA Menu and cycling through the variables
by pressing the green
►
button . If you see values labeled FL,
TL, AFR and TOL, then the option is installed.
• Adjust the tolerance for leak detection to be either more or less
forgiving in recognizing a problem.
• The default tolerance is 75% That is, Gen 1.3 will not detect
and annunciate a leak until the Actual Volume is more than
175% of the Calculated Volume.
• Setting the TOL value in the DATA Menu to a higher number
makes the unit more tolerant of a leak. Setting the TOL value
lower makes the unit more sensitive. 100% is the allowed
maximum.
• To change the value, go to the DATA Menu, TOL. Press
Green
►
button for 5 seconds, then use the arrow keys to
adjust the value.
• Disable leak detection by 1) unplugging the unit from the
electrical socket, 2) unplugging the 6 pin connector on the back of
the controller, and 3) plugging the unit back into the electrical
socket.
• NOTE: Leak Detection may not function properly on systems with
less than 20 nozzles and/or mist durations less than 30 seconds.
Optional Leak Detection
Section 3
Setting Up the Unit
• Clear area
• Pres MIST button on transmitter
• Unit will MIST.
•
If Remote Agitation (RAG) is set to a
value greater than 0, system with
Agitate (AGT) prior to MIST.
12. Test by Activating
Remote Mist
• Close lid
• Fit elastic at waterproof cover
bottom under lip along edge of drum.
13. Cover Unit
Section 3
Setting Up the Unit
• Add insecticide through large bung
with a funnel.
• Top off drum with water. Maintain
air gap of 6” between hose and fluid
level.
• Do not overfill. Stop filling when
level is 4” from the top.
• MAINTENANCE Menu, LEVEL
• Press green
►
button and use
arrows to set level to full (8 bars)
10. Add insecticide, top
off drum, Reset
LEVEL to full
• MAINTENANCE Menu, scroll to INS
• Depress Green
►
button 5 seconds
• Unit will mist for 5 minutes or until
stopped.
• Confirm no leaks in nozzle circuit.
• Confirm pump pressure is 240 psi.
If not, insert flat head screwdriver
into port on back left and adjust
pump bypass until pressure is 240
psi. Reinsert plastic plug into port.
• If zone valve installed, repeat using
INS2. (Set pressure so that it does
not exceed 240 psi in either zone.)
9.
Run Inspection Cycle
• With the display showing day, time
and level, press Green
►
button to
position the
▲
at top of display
pointing to the active System Mode:
• OFF - daily agitation cycle only
• REM or ON – remote and manual,
but no programmed mist
• AUTO Everyday – program runs
daily. This is the usual mode.
• AUTO Custom – program runs on
days configured in CUSTOM PGM
11. Set System Mode