Analog Scaling Setup
• Channel: alternate between analog input channels
• Offset: allows you to enter value if sensor is not at the bottom or top of
measured item
• Range: of sensor as described on the instrument name plate, or converted
value appropriate to engineering units. For example, 2.31 feet per PSI results
in a 0–23.1’ range on a 0–10 PSI pressure transducer.
• Units: engineering units as desired
Auxiliary Output Voltage:
• 0, 12, 24 VDC
• Make certain all items powered by auxiliary are compatible to this selection
Relay Communication Failure:
• De-energize: generally appropriate if pumping into a pressure tank
• No change: generally appropriate if tank can spill
• See Best Practices for Remote Control Applications document
Battery Test:
• Runs a routine that puts battery under load and returns final voltage. This test
is performed daily and recorded on web portal.
• A good battery should result in a V-battery test reading of 12.1–12.4 volts,
assuming it as been installed and properly charged.
Server Connection:
Tech support will advise if it should be changed from default.
Miscellaneous
• Language
• Temperature (C or F)
• Audio
• Screen Saver
Configurable Settings NOT Shown on the LCD
Alarm threshold settings must be paged to the RTU.