19
Chapter 4: Test the MyDro After Installation
and Commissioning
1. Check input voltages with a multi-meter.
2. Exercise all inputs and confirm that the LCD and web portal are displaying
the values correctly. Page relays and analog output (if in use) from the web
portal and confirm proper operation. As a reminder, the N/O and N/C termi-
nals on the output relays are opposite that of the Legacy RTU.
3. Confirm all automated remote control functions are working properly.
4. Confirm all fail-safe operations are working as desired. One way to do this is
to disconnect the antenna so that the RTU goes offline.
5. Contact Mission Technical Support so that we can associate the new radio
identifier (IMEI) with the data from the previous RTU.