The recommended standoff height is 150 mm. If other mounting means are employed this may affect the UL Listing or
the fire class ratings.
•
Minimum slope of 5 in/ft for installation over a roof is required to maintain the fire class ratings.
•
The PV modules are designed for a maximum altitude of 2000m.
•
Artificially concentrated sunlight should not be directed on the module.
•
Rated electrical characteristics are within 10 percent of measured values at Standard Test Conditions of: 1000 W/m2,
25°C cell temperature and solar spectral irradiance as per IEC 60904-3
•
Under normal conditions, a photovoltaic module may experience conditions that produce more current and/or voltage
than reported at Standard Test Conditions. Accordingly, the values of I
SC
should be multiplied by a factor of 1.25 and V
OC
by a factor of up to 1.25 when determining component voltage ratings, conductor capacities, fuse sizes and size of
controls connected to the module output.
•
Refer to Section 690-8 of the National Electric Code for an additional multiplying factor of 1.25 which may be applicable.