6
Connections and Settings
Power Converter and Trouble Relay Module (Model PCS-100)
The PCS-100 and a 3G4010 Wireless Alarm Communicator is required when using a wireless telephone line as a
second line (Line 2). As per CAN/ULC S559 Equipment for Fire Signal Receiving Centres and Systems Standard
for “non-interdependent passive communication systems” you must wire line 1 as a land line and line 2 as wireless
using the PCS-100 and the 3G4010.
Figure 3: Power Converter and Trouble Relay module
The following hardware configuration must be performed before installing the PCS-100.
Table 3: PCS-100 Jumper Setting
JW1
This jumper is factory set to connect the top two pins, 1 and 2. This detects a
trouble on the high signal and the trouble relay is normally open. If the jumper
is moved to the lower two pins 2 and 3, a trouble is detected on the low signal
and the trouble relay is normally closed.
PGM4 GND 14V
NO COM NC
24V GND
JW1
1
2
3
TRL-HIGH
PGM4
TBL-LOW