14
Configuration Set-up
4. Power up the fire alarm panel and the message of the CFG-300 Configuration Tool should be:
5. Place jumper on JW2, located in the bottom right hand corner of the DTC-300A-2 board (this will generate a
trouble on the DTC-300A-2 and report this to the receiver). Press Menu on the keypad to enter the
configuration menu and configure the DTC-300A-2. The following screen will ask for the passcode.
6. Enter the default passcode, 1111. Press Enter.
CONFIGURATION VIA UIMA AND COMPUTER(LOCAL):
1. Set-up UIMA connection: the 10-pin cable connector of UIMA is connected to P2 on DTC-300A-2 board. A
serial cable or USB cable is needed to connect the UIMA to the computer.
2. Place a jumper at JW2 on the DTC-300A-2 board to allow the configuration (a trouble is generated and
reported to the receiver DACR).
3. Start the Mircom Software MSW-012 on the computer to configure the DTC-300A-2. Follow the instructions of
MSW-012 menu to complete the configuration of the DTC-300A-2.
4. Remove jumper on JW2 after configuration is finished, otherwise a trouble will occur.
CONFIGURATION VIA MODEM AND COMPUTER(REMOTE):
1. Set-up the modem connection on the computer. Make sure the phone line is working properly.
2. Place a jumper at JW2 on the DTC-300A-2 board to allow the configuration (a trouble is generated and
reported to the receiver DACR).
3. Start the Mircom Software MSW-012 on the computer to configure the DTC-300A-2. Follow the instructions of
MSW-012 menu to complete the configuration of the DTC-300A-2.
4. Remove jumper on JW2 after configuration is finished, otherwise a trouble will occur.
S/DTC-300A Idle
00:00 SUN 2006-10-01
Enter Passcode
Passcode:_