DTC-300A-2 Dialer Installation and Operation Instructions
31
Specifications
All Circuits are Power Limited except 24V DC OUT
DTC-300A-2 Digital Communicator
• Connects to two Telephone land Lines or one land line and one
DCS
3G4010
with a PCS-100 (ULC) and
performs line supervision.
• Connects to a FACP via input zones and 24V DC regulated or 24V FWR power.
• Transmits user configurable Alarm, Supervisory, and Trouble status to a DACR, using either Ademco Contact
ID or SIA DCS protocols.
• User configurable locally or remotely. Configuration is passcode protected.
• Current Consumption:
Standby
: 650 mA
Alarm
: 670 mA with PCS-100
• 0 to 49 degrees Celsius, 93 percent humidity.
• Refer to CAN/ULC-S536, Standard for the Inspection and Testing of Fire Alarm Systems for testing and
maintenance procedures.
Battery Calculations
DTC-300A-2
The DTC-300A-2 Battery Calculations are performed as part of the calculations for the Fire Alarm Panel it will be
used with. See the appropriate Fire Alarm Control Panel Manual.