3  Installation and Operation 

(QUALIFIED SERVICE PERSONNEL ONLY) 

Be sure to read the Installation Placement and all of the 

CAUTIONS 

and the 

WARNINGS

 before installing the UPS system. Place the UPS, the Isolation 

Transformer and the Battery Pack in the final desired location and complete the 
rest of the installation procedure. 

 

3.1. 

Unpacking 

 

Remove the UPS, Isolation Transformer and Battery Pack from the packing 
boxes. 

USE CAUTION:

 This UPS system is extremely heavy. Always use the 

appropriate number of personnel when installing the UPS system. After 
removing your UPS, Isolation Transformer and Battery Pack from the packing 
boxes, it should be inspected for damage that may have occurred in shipping. 
Immediately notify the carrier and place of purchase if any damage is found. 
The packing materials that your UPS system was shipped in are carefully 
designed to minimize any shipping damage. In the unlikely case that the UPS 
system needs to be returned to the manufacturer, please use the original 
packing material. Since the manufacturer is not responsible for shipping 
damage incurred when the system is returned, the original packing material is 
inexpensive insurance. 

PLEASE SAVE THE PACKING MATERIALS!

 

 

3.1.1  Standard Package includes: 

 

User's Manual 

 

Warranty and Platinum Protection documents 

 

Power Monitoring software CD with RS232 cable 

 

1-package of accessories 

 

Battery Cable and interconnecting cables 

 
 
 
 
 
 
 
 
 
 
 
 

 
 
 

A1

A2

A3

S1

S2

S3

S4

B1

B2

C1

C2

B3

R1

R2

 

 

 

13

3.2. 

Installation Placement 

 
This UPS system is intended to be install in a temperature controlled 
environment that is free of conductive contaminants. Select a location, which 
will provide good air circulation for the UPS at all times. Keep at least 12 
inches (30cm) clearance from the rear panel of the UPS to the wall. Avoid 
locations near heating devices, water or excessive humidity, or where the 
UPS is exposed to direct sunlight. Route power cords so they cannot be 
walked on or damaged. 

 

 

 

 

 
 

3.3. 

Storage Instruction 

 

For extended storage with moderate climates, the batteries should be 
charged for 12-hours every 3 months. Repeat this procedure every 2 months 
under high temperature environments. 

 

AIR

AIR

C

0

0

C

40

0

Relative Humidly 
(non condensation) 30%~90% 

Содержание ED6200RM

Страница 1: ...tems Inc 1455 LeMay Drive Carrollton TX 75007 Phone 1 972 446 7363 Fax 1 972 446 9011 Internet minutemanups com UPS Sizing sizemyups com PN 34000315 R5 ED6200RM Parallel Redundant ON LINE SERIES User...

Страница 2: ...Installation of Castor Covers 14 3 5 Wiring the Input and Output Connections 18 3 6 RJ 45 cables for the Maintenance Bypass Operation 27 3 7 Operation and Setup Instructions 28 4 Communication Port EP...

Страница 3: ...enance of the UPS and batteries 1 1 12 CAUTION A disconnect switch must be provided by the user for the AC output circuit when the UPS s output is hardwired To reduce the risk of fire connect only to...

Страница 4: ...Parallel Redundant kit Contact your local distributor for more information concerning the Parallel Redundant operation 2 2 5 Maintenance Bypass Switch which reduces down time for maintenance 2 2 6 The...

Страница 5: ...Er03 PFC Boost soft start abnormal after 30 seconds 30 Er04 Inverter Failure 31 Er05 Battery Weak or Dead 32 Er06 Output Short Circuit 33 Er08 DC Bus high voltage level abnormal 34 Er09 DC Bus low vol...

Страница 6: ...59 CEr2 Bypass Voltage out of range 60 CEr3 Inverter Voltage out of range 61 CEr4 Load Percentage out of range 62 CEr5 Battery Voltage out of range 63 CEr6 UPS Output Voltage out of range Er7 Er19 Er2...

Страница 7: ...nnecting a Battery Pack G Cooling Fans H Terminal block for Input Output power connection I Option Slot 1 is for other option cards except the SNMP card and the Programmable Relay card J Option Slot 2...

Страница 8: ...cking material Since the manufacturer is not responsible for shipping damage incurred when the system is returned the original packing material is inexpensive insurance PLEASE SAVE THE PACKING MATERIA...

Страница 9: ...Pack and then connect UPS and the Battery Pack together S1 A3 S3 15 3 4 1 2 UPS Isolation Transformer and Battery Pack 3 4 2 Rack Installation 3 4 2 1 UPS Isolation Transformer and Battery Pack Step1...

Страница 10: ...ion Transformer and Battery Pack Step3 Install the Rails in the 4 post Rack S3 S3 17 Step4 Install the Battery Pack to the Rails Step5 Install the Rails in the 4 post Rack and then install the Isolati...

Страница 11: ...current protection device in accordance with the National Electric Code ANSI NFPA 70 Use 60 C copper wire and apply 22 1lb in of torque force when connecting to the terminal blocks Output Voltage and...

Страница 12: ...put of the Isolation Transformer A Qualified Electrical Contractor must perform the hardwiring The outputs must be connected to an over current protection device circuit breaker in accordance with the...

Страница 13: ...rom L22 to N11 L11 L1 N22 L2 G Earth Ground 240Vac 23 3 5 2 3 9 Configuration 5 Output Two separate circuits of 120VAC 3KVA loads 3KVA max load per circuit Total combined output load not to exceed 6KV...

Страница 14: ...e box to the TR OUTPUT terminal block 4 Has a Maintenance Bypass Switch see Section 3 6 for connecting the RJ 45 cables for the Maintenance Bypass operation 25 3 5 3 1 Application B 1 Utility Input 20...

Страница 15: ...L21 2 Connect a wire to the Output terminal N22 3 Connect a wire to the Output terminal G2 3 5 4 3 Application D 1 Utility Input 208 240VAC must be hardwired see Section 3 5 4 1 for wiring 2 UPS Outpu...

Страница 16: ...n Switch on the front panel for approximately 3 seconds then release The audible alarm will sound 2 beeps then the LCD display will change from drawing B to drawing C C 29 3 7 1 6 The UPS will perform...

Страница 17: ...release the audible alarm will sound 2 beeps The LCD display will change from drawing G to drawing H the UPS will be in self test mode The UPS will provide an output within approximately 1 minute and...

Страница 18: ...1 Once the UPS has successfully started up press the Special Function keypad to change the LCD display screen to drawing Q1 Q1 It shows the Buzzer is Enabled Q2 It shows the Buzzer is Disabled 3 7 4 2...

Страница 19: ...ws the bypass voltage is adjusted to the higher limit T It shows the Frequency Window is 3Hz 35 U It shows the Inverter Output Voltage setting V1 It shows the UPS is operated in the Normal mode V2 It...

Страница 20: ...can be changed to 184VAC 260VAC or 195VAC 260VAC 3 7 5 4 Drawing T means the bypass frequency window of the Inverter Output can be changed to 3Hz or 1Hz 3 7 5 5 Drawing U means the Inverter Output Vo...

Страница 21: ...PS system 3 7 8 1 1 Press the Off switch for approximately 5 seconds the LCD screen will display drawing B and the UPS will be in the Bypass mode 3 7 8 1 2 Remove the Maintenance Bypass Switch cover f...

Страница 22: ...UPS shuts down the fans will still be on In approximately 1 minute the fans will reduce speed To restart the UPS once the utility power returns Press the Off switch on the front panel for 2 beeps then...

Страница 23: ...43 7 Replacing the Batteries QUALIFIED SERVICE PERSONNEL ONLY Please read all of the WARNINGS and CAUTIONS before attempting to service the batteries WARNING This Uninterruptible Power Supply contains...

Страница 24: ...el of the UPS 7 1 4 Turn Off the utility power circuit breaker at the service panel 7 1 5 Disconnect all of the communications and network cables from the rear panel of the UPS 7 1 6 Turn Off the DC c...

Страница 25: ...reaker on the rear panel of the UPS if applicable 7 1 34 Press and hold the On Switch on the front panel for approximately 3 seconds then release if applicable 7 1 35 Turn On the equipment that is con...

Страница 26: ...tripped A tripped circuit breaker is the most common problem Call your dealer for assistance If you cannot reach your dealer or if they cannot resolve the problem call or fax MINUTEMAN Technical Suppo...

Страница 27: ...Except as provided herein Para Systems makes no warranties expressed or implied including warranties of merchantability and fitness for a particular purpose Some states do not permit limitation of imp...

Отзывы: