![Minuteman ED6200RM Скачать руководство пользователя страница 8](http://html1.mh-extra.com/html/minuteman/ed6200rm/ed6200rm_user-manual_1804366008.webp)
12
3 Installation and Operation
(QUALIFIED SERVICE PERSONNEL ONLY)
Be sure to read the Installation Placement and all of the
CAUTIONS
and the
WARNINGS
before installing the UPS system. Place the UPS, the Isolation
Transformer and the Battery Pack in the final desired location and complete the
rest of the installation procedure.
3.1.
Unpacking
Remove the UPS, Isolation Transformer and Battery Pack from the packing
boxes.
USE CAUTION:
This UPS system is extremely heavy. Always use the
appropriate number of personnel when installing the UPS system. After
removing your UPS, Isolation Transformer and Battery Pack from the packing
boxes, it should be inspected for damage that may have occurred in shipping.
Immediately notify the carrier and place of purchase if any damage is found.
The packing materials that your UPS system was shipped in are carefully
designed to minimize any shipping damage. In the unlikely case that the UPS
system needs to be returned to the manufacturer, please use the original
packing material. Since the manufacturer is not responsible for shipping
damage incurred when the system is returned, the original packing material is
inexpensive insurance.
PLEASE SAVE THE PACKING MATERIALS!
3.1.1 Standard Package includes:
User's Manual
Warranty and Platinum Protection documents
Power Monitoring software CD with RS232 cable
1-package of accessories
Battery Cable and interconnecting cables
A1
A2
A3
S1
S2
S3
S4
B1
B2
C1
C2
B3
R1
R2
13
3.2.
Installation Placement
This UPS system is intended to be install in a temperature controlled
environment that is free of conductive contaminants. Select a location, which
will provide good air circulation for the UPS at all times. Keep at least 12
inches (30cm) clearance from the rear panel of the UPS to the wall. Avoid
locations near heating devices, water or excessive humidity, or where the
UPS is exposed to direct sunlight. Route power cords so they cannot be
walked on or damaged.
3.3.
Storage Instruction
For extended storage with moderate climates, the batteries should be
charged for 12-hours every 3 months. Repeat this procedure every 2 months
under high temperature environments.
AIR
AIR
C
0
0
C
40
0
Relative Humidly
(non condensation) 30%~90%