3.5.2.3.2 Connect the wires from the 208V/240V receptacle box (ED6-208RB) as
follows (Output voltage 208V):
1. Connect the Black wire labeled L12 to terminal L12.
2. Connect the White jumper wire from N11 to terminal L22.
3. Connect the White wire labeled N22 to terminal N22.
4. Connect the Green/Yellow wire labeled G to terminal G.
3.5.2.3.3 Connect the wires from the 208V/240V receptacle box (ED6-208RB) as
follows (Output voltage 240V):
1. Connect the Black wire labeled L12 to terminal L11.
2. Connect the White jumper wire from N11 to terminal L22.
3. Connect the White wire labeled N22 to terminal N22.
4. Connect the Green/Yellow wire labeled G to terminal G.
3.5.2.3.4 Hardwiring the TR OUTPUT:
Configurations 1 – 7 are for Hardwiring the output of the Isolation Transformer.
A Qualified Electrical Contractor must perform the hardwiring.
The outputs
must be connected to an over-current protection device (circuit breaker) in
accordance with the National Electric Code, ANSI/NFPA 70. Use 60
°
C copper
wire and apply 22.1lb-in of torque force when connecting to the terminal blocks.
Note:
See the Output Voltage and Load Table for Output Circuit Breaker and
Wire sizes.
21
3.5.2.3.5 Configuration
1.
Output: 208VAC 6KVA max load and two separate circuits of 120VAC 3KVA
loads (3KVA max load per circuit). Total combined output load not to exceed
6KVA. Connect a jumper wire from L22 to N11.
Circuit1: L22-Line, N22-Neutral, G-Earth Ground.
Circuit2: L11-Line, N11-Neutral, G-Earth Ground.
Circuit3: L12-L1, N22-L2, G-Earth Ground.
3.5.2.3.6 Configuration
2.
Output: 208VAC single 6KVA load. Total output load not to exceed 6KVA.
Connect a jumper wire from L22 to N11.
L12-L1, N22-L2, G-Earth Ground.
208Vac