24
3.5.2.3.11 Configuration 7.
Output: 208VAC 6KVA load, 240VAC 6KVA load and two separate circuits of
120VAC 3KVA loads (3KVA max load per circuit). Total combined output load
not to exceed 6KVA. Connect a jumper wire from L22 to N11.
Circuit1: L22-Line, N22-Neutral, G-Earth Ground.
Circuit2: L11-Line, N11-Neutral, G-Earth Ground.
Circuit3: L12-L1, N22-L2, G-Earth Ground.
Circuit4: L11-L1, N22-L2, G-Earth Ground.
120Vac
208Vac
240Vac
120Vac
3.5.3 Application
A:
1. Utility Input: 208/240VAC must be hardwired (see Section 3.5.1 for wiring).
2. TR Output: 208VAC or 240VAC and 120VAC.
3. Output Receptacle Box (ED6-120RB): 1)-L6-30R, 1)-L5-30R, 1)-L5-20R
and 2)-5-15/20R (see Section 3.5.2.3 for wiring the receptacle box to the
TR OUTPUT terminal block).
4. Has a Maintenance Bypass Switch (see Section 3.6 for connecting the RJ-
45 cables for the Maintenance Bypass operation).
25
3.5.3.1 Application
B:
1. Utility Input: 208/240VAC must be hardwired (see Section 3.5.1 for wiring).
2. TR Output: 208VAC, 240VAC and 120VAC hardwired (see Section
3.5.2.3.4 for wiring the TR OUTPUT terminal block).
3. Has a Maintenance Bypass Switch (see Section 3.6 for connecting the RJ-
45 cables for the Maintenance Bypass operation).
3.5.3.2 Application
C:
1. Utility Input: 208/240VAC must be hardwired (see section 3.5.1 for wiring).
2. TR Output: 208VAC or 240VAC.
3. Output Receptacle Box (ED6-208RB): 1)-L6-30R, 1)-L6-20R and 4)-6-
15/20R (see Section 3.5.2.3 for wiring the receptacle box to the TR
OUTPUT terminal block).
4. Has a Maintenance Bypass Switch (see Section 3.6 for connecting the RJ-
45 cables for the Maintenance Bypass operation).