Minuteman ED6200RM Скачать руководство пользователя страница 25

 

46

7.1.14  Gently remove the top part of the plastic battery tray. 
7.1.15  Disconnect the red battery wire from the battery terminal. 
7.1.16  Disconnect the black battery wire from the battery terminal. 
7.1.17  Disconnect the 3-battery jumper wires from the battery terminals. 
7.1.18  Remove the 4-defective batteries from the battery tray and set aside. 
7.1.19  Install the 4-new batteries in the battery tray in the same position as the 

original batteries. 

7.1.20 Observe polarity. Reconnect the 3-battery jumper wires to the battery 

terminals. 

7.1.21  Observe polarity. Reconnect the black battery wire to the battery terminal. 
7.1.22  Observe polarity. Reconnect the red battery wire to the battery terminal. 
7.1.23  Reinstall the top part of the plastic battery tray on top of the batteries. 

NOTE: 

Make sure that all of the battery wires remain on top of the batteries and 

inside the plastic battery tray. 
7.1.24  Reinstall the battery tray in the Battery Pack module. 

USE CAUTION: 

The 

battery trays are extremely heavy. 

NOTE: DO NOT

 pinch the battery wires between the batteries and the Battery Pack 

chassis. 
7.1.25  Reconnect the red and black Anderson battery connectors. 
7.1.26  Install new cable ties through the holes in the battery tray then around the 

battery wires (see 7.1.11). 

7.1.27  Once all the battery trays are complete reinstall the front panel. 
7.1.28  Reinstall the front panel retaining screws. 
7.1.29  Reconnect all of the communications and network cables (if applicable). 
7.1.30  Reconnect the battery cables (if applicable). 
7.1.31  Turn On the DC circuit breaker (s) on the rear panel of the Battery Pack 

module (s). 

7.1.32  Turn On the utility power circuit breaker at the service panel (if applicable). 
7.1.33  Turn On the input circuit breaker on the rear panel of the UPS (if applicable). 
7.1.34  Press and hold the On Switch (on the front panel) for approximately 3-

seconds, then release (if applicable). 

7.1.35  Turn On the equipment that is connected to the UPS (if applicable). 
7.1.36  The UPS system is now ready for the normal operation. 
7.1.37  Properly dispose of the old batteries at an appropriate recycling facility or 

return them to the supplier in the packing material for the new batteries. 

 

 

47

8 Specifications 

 

MODEL 

ED6200RM 

Topology 

Double Conversion On-Line, True Sine Wave 

Maximum Power Capacity 

6000VA/4200Watts 

INPUT 

Number of Phases 

Single (1Ø 2W +G) 

Nominal Voltage 

208VAC 

Acceptable Input Voltage 

0 - 300VAC 

Voltage Range 

160* - 280VAC 

Power Factor Correction 

>98% at Full Load 

Frequency Limits 

50/60Hz +/-5Hz autosensing 

Low Voltage Transfer Point 

160V resets to utility power at 175V or higher 

High Voltage Transfer Point 

280V resets to utility power at 265V or lower 

Protection 

Re-settable Circuit Breaker 

OUTPUT 

Waveform Type 

True Sine Wave 

Nominal Voltage with Isolation 
Transformer 

120VAC and 208/240VAC 

Nominal Voltage without 
Isolation Transformer 

 

208/240VAC 

Voltage Regulation   

+/-2% (until Low Battery Warning) 

Frequency   

50/60Hz +/-0.2Hz (unless synchronized to utility) 

Voltage T.H.D. 

<3% (Linear load) 

Dynamic Response 

+/-5% @ 100% Load change in 100ms 

Transfer Time   

0ms 

Slew Rate 

<1Hz / second 

Efficiency (Line Mode)   

>87% (Full Load) 

Crest Factor 

3 : 1 

Overload Capacity 

>105% - <155% for 160 seconds 

>156% shutdown immediately 

Protection 

Over-Current, Short-Circuit and Latching Shutdown 

SURGE PROTECTION AND FILTERING 

Surge Energy Rating 

1050 J 

Surge Energy Capability 

6500 Amps total 

Surge voltage let-through (as a 
percentage of an applied ANSI 
C62.41 Cat. A +/-6KV) 

 

<5% 

Noise Filter 

Normal and common mode EMI/RFI suppression 

Audible Noise at 1 m (3 ft.) 

<50dB 

* 160 – 280VAC at loads <50% of the rated capacity 
* 175 – 280VAC at loads <75% of the rated capacity 
* 180 – 280VAC at loads >75% of the rated capacity

 

Содержание ED6200RM

Страница 1: ...tems Inc 1455 LeMay Drive Carrollton TX 75007 Phone 1 972 446 7363 Fax 1 972 446 9011 Internet minutemanups com UPS Sizing sizemyups com PN 34000315 R5 ED6200RM Parallel Redundant ON LINE SERIES User...

Страница 2: ...Installation of Castor Covers 14 3 5 Wiring the Input and Output Connections 18 3 6 RJ 45 cables for the Maintenance Bypass Operation 27 3 7 Operation and Setup Instructions 28 4 Communication Port EP...

Страница 3: ...enance of the UPS and batteries 1 1 12 CAUTION A disconnect switch must be provided by the user for the AC output circuit when the UPS s output is hardwired To reduce the risk of fire connect only to...

Страница 4: ...Parallel Redundant kit Contact your local distributor for more information concerning the Parallel Redundant operation 2 2 5 Maintenance Bypass Switch which reduces down time for maintenance 2 2 6 The...

Страница 5: ...Er03 PFC Boost soft start abnormal after 30 seconds 30 Er04 Inverter Failure 31 Er05 Battery Weak or Dead 32 Er06 Output Short Circuit 33 Er08 DC Bus high voltage level abnormal 34 Er09 DC Bus low vol...

Страница 6: ...59 CEr2 Bypass Voltage out of range 60 CEr3 Inverter Voltage out of range 61 CEr4 Load Percentage out of range 62 CEr5 Battery Voltage out of range 63 CEr6 UPS Output Voltage out of range Er7 Er19 Er2...

Страница 7: ...nnecting a Battery Pack G Cooling Fans H Terminal block for Input Output power connection I Option Slot 1 is for other option cards except the SNMP card and the Programmable Relay card J Option Slot 2...

Страница 8: ...cking material Since the manufacturer is not responsible for shipping damage incurred when the system is returned the original packing material is inexpensive insurance PLEASE SAVE THE PACKING MATERIA...

Страница 9: ...Pack and then connect UPS and the Battery Pack together S1 A3 S3 15 3 4 1 2 UPS Isolation Transformer and Battery Pack 3 4 2 Rack Installation 3 4 2 1 UPS Isolation Transformer and Battery Pack Step1...

Страница 10: ...ion Transformer and Battery Pack Step3 Install the Rails in the 4 post Rack S3 S3 17 Step4 Install the Battery Pack to the Rails Step5 Install the Rails in the 4 post Rack and then install the Isolati...

Страница 11: ...current protection device in accordance with the National Electric Code ANSI NFPA 70 Use 60 C copper wire and apply 22 1lb in of torque force when connecting to the terminal blocks Output Voltage and...

Страница 12: ...put of the Isolation Transformer A Qualified Electrical Contractor must perform the hardwiring The outputs must be connected to an over current protection device circuit breaker in accordance with the...

Страница 13: ...rom L22 to N11 L11 L1 N22 L2 G Earth Ground 240Vac 23 3 5 2 3 9 Configuration 5 Output Two separate circuits of 120VAC 3KVA loads 3KVA max load per circuit Total combined output load not to exceed 6KV...

Страница 14: ...e box to the TR OUTPUT terminal block 4 Has a Maintenance Bypass Switch see Section 3 6 for connecting the RJ 45 cables for the Maintenance Bypass operation 25 3 5 3 1 Application B 1 Utility Input 20...

Страница 15: ...L21 2 Connect a wire to the Output terminal N22 3 Connect a wire to the Output terminal G2 3 5 4 3 Application D 1 Utility Input 208 240VAC must be hardwired see Section 3 5 4 1 for wiring 2 UPS Outpu...

Страница 16: ...n Switch on the front panel for approximately 3 seconds then release The audible alarm will sound 2 beeps then the LCD display will change from drawing B to drawing C C 29 3 7 1 6 The UPS will perform...

Страница 17: ...release the audible alarm will sound 2 beeps The LCD display will change from drawing G to drawing H the UPS will be in self test mode The UPS will provide an output within approximately 1 minute and...

Страница 18: ...1 Once the UPS has successfully started up press the Special Function keypad to change the LCD display screen to drawing Q1 Q1 It shows the Buzzer is Enabled Q2 It shows the Buzzer is Disabled 3 7 4 2...

Страница 19: ...ws the bypass voltage is adjusted to the higher limit T It shows the Frequency Window is 3Hz 35 U It shows the Inverter Output Voltage setting V1 It shows the UPS is operated in the Normal mode V2 It...

Страница 20: ...can be changed to 184VAC 260VAC or 195VAC 260VAC 3 7 5 4 Drawing T means the bypass frequency window of the Inverter Output can be changed to 3Hz or 1Hz 3 7 5 5 Drawing U means the Inverter Output Vo...

Страница 21: ...PS system 3 7 8 1 1 Press the Off switch for approximately 5 seconds the LCD screen will display drawing B and the UPS will be in the Bypass mode 3 7 8 1 2 Remove the Maintenance Bypass Switch cover f...

Страница 22: ...UPS shuts down the fans will still be on In approximately 1 minute the fans will reduce speed To restart the UPS once the utility power returns Press the Off switch on the front panel for 2 beeps then...

Страница 23: ...43 7 Replacing the Batteries QUALIFIED SERVICE PERSONNEL ONLY Please read all of the WARNINGS and CAUTIONS before attempting to service the batteries WARNING This Uninterruptible Power Supply contains...

Страница 24: ...el of the UPS 7 1 4 Turn Off the utility power circuit breaker at the service panel 7 1 5 Disconnect all of the communications and network cables from the rear panel of the UPS 7 1 6 Turn Off the DC c...

Страница 25: ...reaker on the rear panel of the UPS if applicable 7 1 34 Press and hold the On Switch on the front panel for approximately 3 seconds then release if applicable 7 1 35 Turn On the equipment that is con...

Страница 26: ...tripped A tripped circuit breaker is the most common problem Call your dealer for assistance If you cannot reach your dealer or if they cannot resolve the problem call or fax MINUTEMAN Technical Suppo...

Страница 27: ...Except as provided herein Para Systems makes no warranties expressed or implied including warranties of merchantability and fitness for a particular purpose Some states do not permit limitation of imp...

Отзывы: