OM-240 044 Page 20
4-13. Electrical Service Guide
Failure to follow these electrical service guide recommendations could create an electric shock or fire hazard. These recommenda-
tions are for a dedicated branch circuit sized for the rated output and duty cycle of the welding power source.
60 Hertz Models
Input Voltage (V)
230
460
575
Input Amperes (A) At Rated Output
57
29
23
Max Recommended Standard Fuse Rating In Amperes
1
Time-Delay
2
70
35
25
Normal Operating 3
90
40
35
Min Input Conductor Size In AWG
4
6
10
10
Max Recommended Input Conductor Length In Feet (Meters)
145 (44)
243 (74)
380 (116)
Min Grounding Conductor Size In AWG
4
8
10
10
Reference: 2011 National Electrical Code (NEC) (including article 630)
1 If a circuit breaker is used in place of a fuse, choose a circuit breaker with time-current curves comparable to the recommended fuse.
2 “Time-Delay” fuses are UL class “RK5” . See UL 248.
3 “Normal Operating” (general purpose - no intentional delay) fuses are UL class “K5” (up to and including 60 amps), and UL class “H” ( 65 amps and
above).
4 Conductor data in this section specifies conductor size (excluding flexible cord or cable) between the panelboard and the equipment per NEC Table
310.15(B)(16). If a flexible cord or cable is used, minimum conductor size may increase. See NEC Table 400.5(A) for flexible cord and cable
requirements.
4-14. Placing Jumper Links
!
Disconnect and lockout/tag-
out input power before
installing or moving jumper
links.
Check input voltage available at
site.
1
Jumper Link Label
Check label.
2
Jumper Links
Move jumper links to match input
voltage.
Close access door, or go on to
Section NO TAG.
Tools Needed:
1
3/8 in.
3/8 in.
L1(U)
S−174973−B
GND/PE
3
Connect
GND/PE
Conductor
First.
Input
Contactor
L2(V)
L3(W)
230VOLTS
460VOLTS
575VOLTS
Do not
overtighten
jumper linknuts.