Read Only (Function 0x03 or 0x04)
Register
Description
Type
Min. Unit
Range
4085
THD Voltage L1
word
0.1%
0 ~ 1000
4086
THD Voltage L2
word
0.1%
0 ~ 1000
4087
THD Voltage L3
word
0.1%
0 ~ 1000
4088
Energy Full Flag
word
Energy flag *
bit 7 to 5 = reserved
bit 4 = (-)kVARh
bit 3 = (-) kWh
bit 2 = kVAh
bit 1 = (+)kVARh
bit 0 = (+)kWh
4089
Power Factor L1
word
0.001
0 ~ 1.000
4090
Sign Power Factor L1
word
-
0=Resistive; 1=ind; 2=cap
4091
Power Factor L2
word
0.001
0 ~ 1.000
4092
Sign Power Factor L2
word
-
0=Resistive; 1=ind; 2=cap
4093
Power Factor L3
word
0.001
0 ~ 1.000
4094
Sign Power Factor L3
word
-
0=Resistive; 1=ind; 2=cap
4095
Sign Total Power Factor
word
-
0=Resistive; 1=ind; 2=cap
4096- 4097
Current L1 Max.
dword
0.001A
0 ~ 999.9kA
4098-4099
Reserved
4100- 4101
Current L2 Max.
dword
0.001A
0 ~ 999.9kA
4102-4103
Reserved
4104- 4105
Current L3 Max.
dword
0.001A
0 ~ 999.9kA
4106-4107
Reserved
4108- 4109
Current Ln Max.
dword
0.001A
0 ~ 999.9kA
4110-4111
Reserved
4112- 4113
Voltage L1 Max.
dword
0.1V
0 ~ 999.9kV
4114-4115
Reserved
4116- 4117
Voltage L2 Max.
dword
0.1V
0 ~ 999.9kV
4118-4119
Reserved
*if the energy is full, the bit is set to 1, else bit is 0.