a. Scroll in programming mode until “Ln” is displayed using the UP or DOWN button.
b. This parameter is to display neutral current if the neutral current (Ln) is connected.
c. Press the NEXT button to change. The “PROG” symbol will blink.
d. Press the UP or DOWN button to toggle the symbol “cAL” for calculated value, “MEA” for measured value
or “OFF” to disable.
e.
Press the NEXT button to confirm the new setting.
f. To proceed to the next setting, press the DOWN button.
g.
To exit programming mode, press the PROG button. The user will be prompted to confirm the saving of
settings if change is made. Refer Section 6.16.
a. Scroll until ”ID BRATE PARITY“ is displayed using the UP or DOWN button.
b. Press the NEXT button. The “PROG” and “-” symbol next to “ID” will blink. Use the UP or DOWN button to
change the device ID.
c. Next, press the NEXT button and “-” symbol next to “BRATE” will blink to change baudrate. Repeat step (b)
to change.
d. Press NEXT button to change parity and “-” symbol next to “PARITY” will blink. Repeat step (b) to change.
e.
Then press the NEXT button to confirm new setting. The “PROG” will stop blinking.
f. To proceed next setting press DOWN button. To exit programming mode, press the PROG button. The user
will be prompted to confirm the saving of settings if change is made. Refer Section 6.16.
*- Applicable for DPM380 only
Default value for the communication ID is 1, baudrate is 38400 bps and parity set to none.