Read or write (Function 0x03,0x04 or 0x06)
Register
Description
Range
100
PT ratio primary
100 ~ 33kV
101
PT ratio secondary
no PT, 100 ~ 250V
102
CT ratio primary
5 ~ 9999A
103
CT ratio secondary
5A
104
Interval Demand
60 ~ 1800s
105
Sub-Interval Demand
1 ~ 120
106
System Configuration
0 = 3P4W
1 = 3P3W
107
Backlight setting
0 = OFF
1 = ON
108
Scroll interval
1 - 10 secs
109
System scroll setting
0 = OFF
1 = ON
110
Neutral setting
0 = OFF
1 = Measured
2 = Calculated
111
Minutes
0 - 59 mins
112
Hours
0 - 23 hrs
113
Days
0 - 9999 days
114
Hour-on reset
1 = YES
115
Max. & Min. Demand reset
1 = YES
116
Max. & Min. parameter reset
1 = YES
Register list is based on firmware version 1.06