Air filter 

Clean or replace if restricted. 

Air discharge pipe

 

Realign and assemble if the installation of the air discharging 

pipe failure. Replace if damaged.

 

Unit undersized

 

Determine if the unit is properly sized for the area to be cooled or 

heated.

 

Condenser and Evaporator

 

Clean or replace if restricted.

 

Water shower failure

 

Check the structure of water showering system and clean if 

blocked.

 

Fan motor

 

Check the fan capacitor and replace if not /-10% of 

manufactures rating.

 

Air flow

 

Clean or remove if any barrier is found to block the inlet/outlet 

wind flow of the unit.

 

Less refrigerant

 

Check the tubes for reasons of leakage. Recycle the refrigerant, 

correct the leakage points and recharge.

 

Capillary tube

 

Regulate the flow if capillary tube and make the evaporating 

temperature appropriate if the evaporator is frosted. Replace if 

blocked. Repair joint if leaking.

 

Compressor

 

The inlet and outlet valve of the compressor is damaged, making 

the low pressure connected with the high pressure. The 

refrigerating system can not produce high pressure and low 

pressure. Replace the compressor after checking for the reason.

Cooling or heating 

feels not good 

Heat sources

 

Reduce if too many.

 

No power 

Check the voltage. Call an electrician if no within the limit. 

Wiring

 

Check the terminals. Repair and correct if loose.

 

Temperature setting

 

Check and adjust the temperature setting.

 

Mode setting

 

Check and adjust the mode setting.

 

Compressor

 

Check and replace if the compressor, the over-load protector or 

wiring is broken.

 

Electric heater failure

 

Check and replace if the heater is damaged.

 

Over heat fuse failure

 

Check and replace if the fuse is damaged.

 

No cooling or 

heating. 

Main PCB

 

Check the voltage of main PCB. Replace the main PCB when the 

unit failure in heating mode.

 

Power supply 

The input power supply voltage is too low. Call an electrician if 

not within limits. 

Main PCB

 

Check and replace the main PCB if the compressor relay on PCB 

is shorted or damaged.

 

The unit starts and 

stops frequently. 

Room temperature

 

When the room temperature is too high, the compressor will 

protect.

 

 

 

 

 

 

 

 

Содержание PK-09ER

Страница 1: ...MPK 09ERN2 MPK 10CEN2 MPK 10CRN2 MPK 10EEN2 MPK 10ERN2 MPK 12CEN2 MPK 12CRN2 MPK 12EEN2 MPK 12ERN2 MPK 08CE MPK 08CR MPK 08EE MPK 08ER MPK 09CE MPK 09CR MPK 09EE MPK 09ER MPK 10CE MPK 10CR MPK 10EE M...

Страница 2: ...tem The refrigerant was charged at the factory Be sure to read the safety precautions prior to servicing the unit 1 1 SAFETY PRECAUTIONS 1 When servicing the unit set the POWER SWITCH to OFF and unplu...

Страница 3: ...1 4 CONTROL LOCATIONS For cooling only with electric heater models For cooling only models Remote receiver Timer ON button Push this button to set the Timer On time Timer OFF button Push this button t...

Страница 4: ...button except this button Reset button Press this button to reset all settings to factory settings 2 TROUBLESHOOTING GUIDE 2 1 REFRIGERATION CYCLE DIAGRAM 2 2 ELECTRICAL FUNCTION 2 2 1 Electric Contr...

Страница 5: ...ot operate After the problem is cleared the unit will be ready to operate But if you push the power button the unit will shut the P1 display and shut down 2 2 5 Fan only Mode Function Requirement 2 2...

Страница 6: ...the other is called the Structure Damage ROOM AIRCONDITIONER VOLTAGE LIMITS NAMEPLATE RATING MINIMUM MAXIMUM 220 240V 115V 196V 103V 253V 122V PROBLEM POSSIBLE CAUSE REMEDY Power failure Check the po...

Страница 7: ...nocking sounds continue when running or loose or the motor hums or noise appears to be internal while running Voltage Check voltage Call Supply Authority if not within limits Wiring Check the wire con...

Страница 8: ...utlet valve of the compressor is damaged making the low pressure connected with the high pressure The refrigerating system can not produce high pressure and low pressure Replace the compressor after c...

Страница 9: ...N2 MPK 10CE MPK 10CR MPK2 09CEN1 QB6 MPK2 09CRN1 QB6 MPK2 10CEN1 QB6 MPK2 10CRN1 QB6 MPK2 12CEN1 QB4 MPK2 12CRN1 QB4 MPK2 12CE QB6 MPK2 12CR QB6 3 2 FOR COOLING AND HEATING MODELS MPK 09EEN2 MPK 09ERN...

Страница 10: ...GD Midea Refrigeration Equipment Co Ltd Service manual for K portable Series 9 3 3 ELECTRICAL CONTROL SCHEME...

Страница 11: ...GD Midea Refrigeration Equipment Co Ltd Service manual for K portable Series 10...

Страница 12: ...GD Midea Refrigeration Equipment Co Ltd Service manual for K portable Series 11 3 4 MAIN CONTROL BOARD SCHEME...

Страница 13: ...GD Midea Refrigeration Equipment Co Ltd Service manual for K portable Series 12 3 5 DISPLAY BOARD SCHEME...

Страница 14: ...ord and disconnect the Air pipe from rear of the unit Move the unit to a replace where water can be poured Remove the rubber plug from back of the unit and drainage the water in from the unit Remove t...

Страница 15: ...ssemble the display board assembly just push the clasp and release the assembly Now it is easy to replace the display board Take care to release the connector which connected to the display board 4 4...

Страница 16: ...t for reference when wiring Pay attention to the wires in the enclosure 1 2 3 4 5 6 7 8 9 10 1 Terminate to display board 2 Terminate to condenser fan motor 3 Out put of transformer 4 Terminate to eva...

Страница 17: ...ws fixing the air out frame Lift the frame up then pull the frame forward Remove the screws fixing the fan shell box Remove the fan motor fan scroll and blower wheel from the unit Take care to the wir...

Страница 18: ...emove the screws fixing the evaporator Remove the screws fixing the condenser fan motor bracket Then remove the bracket with condenser fan motor and blower wheel from the unit 4 9 To repair the refrig...

Страница 19: ...rom the cover Then remove the condenser fan scroll Now it is easy to repair the refrigerant system 4 10 To repair the water disposal system or replace the water depth switch or the pump Remove the scr...

Страница 20: ...ve the screw fixing the water switch which controls the water in tank Press the clamp fixing the water switches which control the water in the chassis Press downward here Then remove the screws fixing...

Страница 21: ...GD Midea Refrigeration Equipment Co Ltd Service manual for K portable Series 20 5 Exploded view See attached files 6 Spare parts list See attached files 7 Specification See attached files...

Отзывы: