GD  Midea  Refrigeration  Equipment  Co.  Ltd                                                                      Service  manual  for  K  portable  Series 

2.2.10.1 The maximum length of Timer is 24 

hours and the minimum is 0.5 hours. 

2.2.10.2 TIMER ON function: first turn OFF the 

unit, the unit will be automatically ON at the 

set time. 

2.2.10.3 TIMER OFF function: first turn ON the 

unit, the unit will be automatically OFF at the 

set time. 

2.2.10.4 TIMER ON/OFF function (ON TIMER is 

earlier than OFF TIMER): first turn OFF the 

unit, it will be automatically ON at set time, 

and later be OFF at the set time. 

2.2.10.5 TIMER OFF/ON function (OFF TIMER is 

earlier than ON TIMER): first turn ON the unit, 

it will be automatically OFF at set time, and 

later be ON at the set time. 

2.2.10.6 Timer function execution is applicable 

upon one operation only. 

2.2.10.7 Timer precision is less than 15 minutes. 

2.2.11 Auto restart function 

In case of a sudden power failure, this 

function automatically sets the unit to 

previous settings before the power failure 

when power returns. 

 

2.3 TROUBLESHOOTING GUIDE 

In general, possible trouble is classified in three kinds. One is called Starting Failure which is caused 

from an electrical defect, another is ineffective Air Conditioning caused by a defect in the refrigeration circuit 

and improper application, and the other is called the Structure Damage. 

ROOM AIRCONDITIONER VOLTAGE LIMITS: 

NAMEPLATE RATING 

MINIMUM 

MAXIMUM 

220~240V 

115V 

196V 

103V 

253V 

122V 

 

 

PROBLEM

 

POSSIBLE CAUSE

 

REMEDY

 

Power failure 

Check the power supplier if the power supplier is supplied to the 

unit. Check the power cord and correct if damaged. 

Transformer (Discharge 

transformer before testing) 

Check resistance between the two input/output lines on 

transformer. Replace the transformer if either of the input/output 

is open or the transformer is damaged. 

No power display 

on panel or any one 

of the buttons 

failure. 

Display board or main PCB 

failure 

Check the voltage on display board. Replace the display board if 

it is +5V else replace the main PCB.   

Remote control 

failure.

 

Battery failure 

Check the voltage of battery. Replace batteries if the voltage is 

lower than 2.3V. 

Check voltage. Call an electrician if not within limits. 

Test capacitor.                                              

Replace if not /-10% of manufacture's rating.

 

Check bearings. Replace the motor if the blower wheel cannot 

rotate freely.

 

Fan motor runs 

intermittently 

Cycles on overload. 

Pay attention to any change from high speed to low speed. 

Replace the motor if the speed does not change.

 

Refrigerant 

The amount of the refrigerant is too much, making the 

compressor load too big. Recycle and recharge the refrigerant 

after checking for the reason. 

Compressor stops 

instantly after 

startup. 

Compressor

 

The compressor is blocked inside. Replace after checking for the 

reason.

 

Содержание PK-09ER

Страница 1: ...MPK 09ERN2 MPK 10CEN2 MPK 10CRN2 MPK 10EEN2 MPK 10ERN2 MPK 12CEN2 MPK 12CRN2 MPK 12EEN2 MPK 12ERN2 MPK 08CE MPK 08CR MPK 08EE MPK 08ER MPK 09CE MPK 09CR MPK 09EE MPK 09ER MPK 10CE MPK 10CR MPK 10EE M...

Страница 2: ...tem The refrigerant was charged at the factory Be sure to read the safety precautions prior to servicing the unit 1 1 SAFETY PRECAUTIONS 1 When servicing the unit set the POWER SWITCH to OFF and unplu...

Страница 3: ...1 4 CONTROL LOCATIONS For cooling only with electric heater models For cooling only models Remote receiver Timer ON button Push this button to set the Timer On time Timer OFF button Push this button t...

Страница 4: ...button except this button Reset button Press this button to reset all settings to factory settings 2 TROUBLESHOOTING GUIDE 2 1 REFRIGERATION CYCLE DIAGRAM 2 2 ELECTRICAL FUNCTION 2 2 1 Electric Contr...

Страница 5: ...ot operate After the problem is cleared the unit will be ready to operate But if you push the power button the unit will shut the P1 display and shut down 2 2 5 Fan only Mode Function Requirement 2 2...

Страница 6: ...the other is called the Structure Damage ROOM AIRCONDITIONER VOLTAGE LIMITS NAMEPLATE RATING MINIMUM MAXIMUM 220 240V 115V 196V 103V 253V 122V PROBLEM POSSIBLE CAUSE REMEDY Power failure Check the po...

Страница 7: ...nocking sounds continue when running or loose or the motor hums or noise appears to be internal while running Voltage Check voltage Call Supply Authority if not within limits Wiring Check the wire con...

Страница 8: ...utlet valve of the compressor is damaged making the low pressure connected with the high pressure The refrigerating system can not produce high pressure and low pressure Replace the compressor after c...

Страница 9: ...N2 MPK 10CE MPK 10CR MPK2 09CEN1 QB6 MPK2 09CRN1 QB6 MPK2 10CEN1 QB6 MPK2 10CRN1 QB6 MPK2 12CEN1 QB4 MPK2 12CRN1 QB4 MPK2 12CE QB6 MPK2 12CR QB6 3 2 FOR COOLING AND HEATING MODELS MPK 09EEN2 MPK 09ERN...

Страница 10: ...GD Midea Refrigeration Equipment Co Ltd Service manual for K portable Series 9 3 3 ELECTRICAL CONTROL SCHEME...

Страница 11: ...GD Midea Refrigeration Equipment Co Ltd Service manual for K portable Series 10...

Страница 12: ...GD Midea Refrigeration Equipment Co Ltd Service manual for K portable Series 11 3 4 MAIN CONTROL BOARD SCHEME...

Страница 13: ...GD Midea Refrigeration Equipment Co Ltd Service manual for K portable Series 12 3 5 DISPLAY BOARD SCHEME...

Страница 14: ...ord and disconnect the Air pipe from rear of the unit Move the unit to a replace where water can be poured Remove the rubber plug from back of the unit and drainage the water in from the unit Remove t...

Страница 15: ...ssemble the display board assembly just push the clasp and release the assembly Now it is easy to replace the display board Take care to release the connector which connected to the display board 4 4...

Страница 16: ...t for reference when wiring Pay attention to the wires in the enclosure 1 2 3 4 5 6 7 8 9 10 1 Terminate to display board 2 Terminate to condenser fan motor 3 Out put of transformer 4 Terminate to eva...

Страница 17: ...ws fixing the air out frame Lift the frame up then pull the frame forward Remove the screws fixing the fan shell box Remove the fan motor fan scroll and blower wheel from the unit Take care to the wir...

Страница 18: ...emove the screws fixing the evaporator Remove the screws fixing the condenser fan motor bracket Then remove the bracket with condenser fan motor and blower wheel from the unit 4 9 To repair the refrig...

Страница 19: ...rom the cover Then remove the condenser fan scroll Now it is easy to repair the refrigerant system 4 10 To repair the water disposal system or replace the water depth switch or the pump Remove the scr...

Страница 20: ...ve the screw fixing the water switch which controls the water in tank Press the clamp fixing the water switches which control the water in the chassis Press downward here Then remove the screws fixing...

Страница 21: ...GD Midea Refrigeration Equipment Co Ltd Service manual for K portable Series 20 5 Exploded view See attached files 6 Spare parts list See attached files 7 Specification See attached files...

Отзывы: