background image

GD  Midea  Refrigeration  Equipment  Co.  Ltd                                                                      Service  manual  for  K  portable  Series 

Anti-icing function at cooling mode. 

Temperature sensor err self-diagnose. 

Both temperature mode display 

2.2.4 Protection 

2.2.4.1 The compressor functions protection with 

a delay of three minutes. 

2.2.4.2 Sensor protection at open or short circuit. 

2.2.4.3 Evaporator anti-icing protection at cooling   

mode. 

2.2.4.4 Water full alarm 

        There are two water position switches used in 

the unit. One detects the water depth in the 

chassis and the other detects the water in the 

tank. 

2.2.4.4.1 Water full alarm will be on when the unit 

is standing by or operating. 

2.2.4.4.2 When the water adds up to the first 

position on the chassis, the pump will be 

activated. If the water drops down through 

the position, the pump will be on and stop 

after 2 minutes. 

2.2.4.4.3 When the water adds up to the position 

on the tank, the compressor, outdoor fan 

motor, electric heater and pump will stop 

operation. And the LED will display “P1” while 

the water full lamp flashes at 2Hz. 

2.2.4.4.4 When the water adds up to the second 

position on the chassis and the switch has 

been on for 10 seconds, the whole unit will 

stop operation. The LED will display “P2” and 

the water full lamp will flash at 5Hz. After you 

have clear the problem, you should unplug 

the unit and plug again. Then the unit will be 

ready to operate. 

2.2.4.4.5 When the unit is standing by, if the unit 

displays “P1”, the pump will not operate. After 

the problem is cleared, the unit will be ready 

to operate. But if you push the power button, 

the unit will shut the “P1” display and shut 

down. 

2.2.5 Fan-only Mode Function Requirement 

2.2.5.1 The compressor and outdoor fan are OFF 

at Fan-only mode. 

2.2.5.2 The speed of indoor fan can be optionally 

chosen as High/Mid/Low. 

2.2.6 Cooling Mode Function Requirement 

2.2.6.1 The speed of indoor fan can be optionally 

selected as High/Mid/Low. 

2.2.6.2 The compressor operate as: 

O

C  

ro om t em per ature  (TA)

TS+1

TS

Comp ressor O N

Temp down

Temp up

Co mpressor O FF

 

2.2.7 Drying mode 

2.2.7.1 When the unit starts to operate in Drying 

mode, the compressor will start while the 

room temperature is over 13

o

C. After the 

compressor started, the compressor will 

operate as: 

O

C  

ro om t em per ature  (TA)

13 C

o

Comp ressor and outd o or
fan O N

Temp down

Temp up

Co mpressor and
ou t door fan OFF

15 C

o

 

2.2.7.2 The indoor fan will operate with high   

speed. The outdoor fan will operate with   

compressor.  

2.2.8 Heating mode 

2.2.8.1 The speed of indoor fan can be optionally 

chosen as High/Mid/Low. 

2.2.8.2 Electric heater operate as : 

O

C  

ro om t em per ature  (TA)

TS+1

TS

Elec t ric h eater O FF

Temp down

Temp up

El ec tric h eater O N

 

2.2.9 Temperature display 

2.2.9.1 The setting temperature will be displayed 

in Cooling and Heating mode. The room 

temperature will be displayed in Drying and 

Fan only mode. 

2.2.9.2 The setting temperature range is from 

17

o

C to 30

o

C or 62

o

F to 88

o

F. The display 

temperature range is from 10

o

C to 35

o

C or 

48

o

F to 98

o

F. If the room temperature is lower 

than 10

o

C or 48

o

F, the display will be 10

o

C or 

48

o

F.  

2.2.10 Timer Function 

Содержание PK-09ER

Страница 1: ...MPK 09ERN2 MPK 10CEN2 MPK 10CRN2 MPK 10EEN2 MPK 10ERN2 MPK 12CEN2 MPK 12CRN2 MPK 12EEN2 MPK 12ERN2 MPK 08CE MPK 08CR MPK 08EE MPK 08ER MPK 09CE MPK 09CR MPK 09EE MPK 09ER MPK 10CE MPK 10CR MPK 10EE M...

Страница 2: ...tem The refrigerant was charged at the factory Be sure to read the safety precautions prior to servicing the unit 1 1 SAFETY PRECAUTIONS 1 When servicing the unit set the POWER SWITCH to OFF and unplu...

Страница 3: ...1 4 CONTROL LOCATIONS For cooling only with electric heater models For cooling only models Remote receiver Timer ON button Push this button to set the Timer On time Timer OFF button Push this button t...

Страница 4: ...button except this button Reset button Press this button to reset all settings to factory settings 2 TROUBLESHOOTING GUIDE 2 1 REFRIGERATION CYCLE DIAGRAM 2 2 ELECTRICAL FUNCTION 2 2 1 Electric Contr...

Страница 5: ...ot operate After the problem is cleared the unit will be ready to operate But if you push the power button the unit will shut the P1 display and shut down 2 2 5 Fan only Mode Function Requirement 2 2...

Страница 6: ...the other is called the Structure Damage ROOM AIRCONDITIONER VOLTAGE LIMITS NAMEPLATE RATING MINIMUM MAXIMUM 220 240V 115V 196V 103V 253V 122V PROBLEM POSSIBLE CAUSE REMEDY Power failure Check the po...

Страница 7: ...nocking sounds continue when running or loose or the motor hums or noise appears to be internal while running Voltage Check voltage Call Supply Authority if not within limits Wiring Check the wire con...

Страница 8: ...utlet valve of the compressor is damaged making the low pressure connected with the high pressure The refrigerating system can not produce high pressure and low pressure Replace the compressor after c...

Страница 9: ...N2 MPK 10CE MPK 10CR MPK2 09CEN1 QB6 MPK2 09CRN1 QB6 MPK2 10CEN1 QB6 MPK2 10CRN1 QB6 MPK2 12CEN1 QB4 MPK2 12CRN1 QB4 MPK2 12CE QB6 MPK2 12CR QB6 3 2 FOR COOLING AND HEATING MODELS MPK 09EEN2 MPK 09ERN...

Страница 10: ...GD Midea Refrigeration Equipment Co Ltd Service manual for K portable Series 9 3 3 ELECTRICAL CONTROL SCHEME...

Страница 11: ...GD Midea Refrigeration Equipment Co Ltd Service manual for K portable Series 10...

Страница 12: ...GD Midea Refrigeration Equipment Co Ltd Service manual for K portable Series 11 3 4 MAIN CONTROL BOARD SCHEME...

Страница 13: ...GD Midea Refrigeration Equipment Co Ltd Service manual for K portable Series 12 3 5 DISPLAY BOARD SCHEME...

Страница 14: ...ord and disconnect the Air pipe from rear of the unit Move the unit to a replace where water can be poured Remove the rubber plug from back of the unit and drainage the water in from the unit Remove t...

Страница 15: ...ssemble the display board assembly just push the clasp and release the assembly Now it is easy to replace the display board Take care to release the connector which connected to the display board 4 4...

Страница 16: ...t for reference when wiring Pay attention to the wires in the enclosure 1 2 3 4 5 6 7 8 9 10 1 Terminate to display board 2 Terminate to condenser fan motor 3 Out put of transformer 4 Terminate to eva...

Страница 17: ...ws fixing the air out frame Lift the frame up then pull the frame forward Remove the screws fixing the fan shell box Remove the fan motor fan scroll and blower wheel from the unit Take care to the wir...

Страница 18: ...emove the screws fixing the evaporator Remove the screws fixing the condenser fan motor bracket Then remove the bracket with condenser fan motor and blower wheel from the unit 4 9 To repair the refrig...

Страница 19: ...rom the cover Then remove the condenser fan scroll Now it is easy to repair the refrigerant system 4 10 To repair the water disposal system or replace the water depth switch or the pump Remove the scr...

Страница 20: ...ve the screw fixing the water switch which controls the water in tank Press the clamp fixing the water switches which control the water in the chassis Press downward here Then remove the screws fixing...

Страница 21: ...GD Midea Refrigeration Equipment Co Ltd Service manual for K portable Series 20 5 Exploded view See attached files 6 Spare parts list See attached files 7 Specification See attached files...