Service manual
24
8.9
Gas charging
Procedure:
1. Connect the charge hose to the charging cylinder.
§
Connect the charge hose which you disconnected from the vacuum pump to the valve at the bottom of the
cylinder.
2. Purge the air from the charge hose.
§
Open the valve at the bottom of the cylinder and press the check valve on the charge set to purge the air
(be careful of the liquid refrigerant).
3. Open the valves (Low side) on the charge set and charge the system with liquid refrigerant.
§
If the system cannot be charge with the specified amount of refrigerant, if can be charged with a little at a
time (approximately 150g each time0 while operating the air conditioner in the cooling cycle; however, one
time is not sufficient, wait approximately 1 minute and then repeat the procedure.(pumping down-pin).
4. Immediately disconnect the charge hose from the 3-way valve’s service port.
§
Stopping partway will allow the refrigerant to be discharged.
§
If the system has been charged with liquid refrigerant while operating the air conditioner, turn off the air
conditioner before disconnecting the hose.
5. Mounted the valve stem caps and the service port
§
Use torque wrench to tighten the service port cap to a torque of 18N.m.
§
Be sure to check for gas leakage.
Содержание MSE-07CR
Страница 1: ...Cover MSE 07CR MSE 07HR MSE 09CR MSE 09HR MSE 12CR MSE 12HR MSE 18CR MSE 18HR...
Страница 12: ...Service manual 9 5 Refrigerant cycle diagram Cooling only Heat pump mode...
Страница 14: ...Service manual 11...
Страница 15: ...Service manual 12 7 Schematic diagram and Wiring diagram 7 1 Schematic diagram...
Страница 16: ...Service manual 13 7 2 Wiring diagram MSE 07CR MSE 09CR MSE 12CR...
Страница 17: ...Service manual 14 MSE 07HR MSE 09HR MSE 12HR...
Страница 25: ...Service manual 22 discharged...