25
1) Anti-cold-wind
function.
2) If the compressor stops caused by room temperature rising, indoor fan will be forced to run 127
seconds with breeze. During this period, anti-cold-wind is disabled. After this, anti-cold –wind function is
available.
3) If the machine runs in rating capacity test mode, indoor fan runs with rating speed, and
anti-cold-wind is disabled.
9.7.2 Indoor fan speed can be set as high, medium, low or auto grade, but anti-cold-wind function is preferential.
Auto fan action in heating mode.
9.7.3 After start the operation frequency of compressor submits to following rule:
When the machine runs, if
Δ
Th stays in a zone for 3 minutes, action of frequency is as follow:
Zone A: Elevate the current frequency one grade, and not stop until the maximum grade.
Zone B: Keep the current frequency.
Zone C: Descend the current frequency one grade.
Remark:
Δ
Tcon can be changed among 0, -2,- 4 , the default is 0
A
5.0
4.5
3.0
2.5
D
C
Δ
Th=(ro
om temp
) – (s
etti
ng
Te
m
p
) –
Δ
Tc
on
3.5
B
44
38
37
34
33
24
17
setting fan speed
low fan
breeze
super breeze
fan stop
Evaporator tem
p
Δ
T=(roo
m
temp)
– (s
etti
ng
Te
mp)
medium
2.5
2.0
1.5
1.0
low
high
Содержание MS9A-09HRDN1-QC2
Страница 3: ...10 1 Indoor Unit Error Display 31 10 2 Diagnosis and Solution 32 10 3 Key parts checking 40...
Страница 10: ...7 3 2 Outdoor Unit MOR 09 12HDN1 QC2...
Страница 12: ...9 5 Refrigerant cycle diagram...
Страница 13: ...10 6 Wiring diagram 6 1 Indoor Unit MS9A 09 12HRDN1 QC2...
Страница 14: ...11 6 2 Outdoor Unit MOR 09 12HDN1 QC2...
Страница 40: ...37...