9.4.3 The action of auto fan in fan-only mode is the same as auto fan in cooling mode with 24
℃
setting temperature.
9.5 Cooling Mode
9.5.1 After starting, the operation frequency of compressor submits to following rule.
When the machine is running and
Δ
T(=room temp. – setting temp.) changes, the frequency of compressor will
rise or descend a grade (7 minutes after starting).
After starting, if
Δ
T stays in a zone for 3 minutes, the frequency will change as follow:
Zone A : Current frequency rise a grade till the maximum grade F8.
Zone B: Keep the current frequency of compressor.
Zone C: Descend the current frequency of compressor until F1.
Zone D: Compressor stops after running as the minimum frequency F1 for 60 minutes or
Δ
T is less than -2
℃
.
9.5.2 Indoor heat exchanger anti-freezing function.
If T2 is lower than 0
℃
, the compressor stops and resumes when T2>5
℃
.
9.5.3 Outdoor unit current control in cooling mode(refer to the parameter table)
9.5.4 Rating capacity test function
1) Set the indoor unit with remote controller as: high fan, 17
℃
in cooling mode, then press “TURBO” button
D
-1.0
B
1.0
-0.5
0.5
1.5
C
T1 – 24
medium
3.5
3.0
1.5
1.0
high
low
I3COOL
I2COOL
I1COOL
comp. pause
freq. descends if curr. rises;
freq. remains if curr. descends
running normally
out
door unit
curr
ent
Δ
T=(roo
m
temp)
– (s
etti
ng
Te
mp)
A
Содержание MS9A-09HRDN1-QC2
Страница 3: ...10 1 Indoor Unit Error Display 31 10 2 Diagnosis and Solution 32 10 3 Key parts checking 40...
Страница 10: ...7 3 2 Outdoor Unit MOR 09 12HDN1 QC2...
Страница 12: ...9 5 Refrigerant cycle diagram...
Страница 13: ...10 6 Wiring diagram 6 1 Indoor Unit MS9A 09 12HRDN1 QC2...
Страница 14: ...11 6 2 Outdoor Unit MOR 09 12HDN1 QC2...
Страница 40: ...37...