9
Pressure Test Instructions
Systems are pressure tested to ensure they are:
Pressure testing is hazardous and should be carried out carefully:
Nitrogen and regulation
Dry (oxygen free) nitrogen (OFN) is used to achieve the pressures required for the
pressure tests because it is inert. You must
never
use oxygen for pressure testing -
pure oxygen at high pressure reacts violently with oil and will explode.
Using the nitrogen regulator
to the pressure required.
Do not use a regulator with an
output pressure much higher
The pressure tests
Increase the pressure to approximately 5 bar g and check for leaks using leak
detection spray at this pressure initially – many leaks will be identified at this
pressure so you will not waste nitrogen and time. It is also safer to find leaks at a
lower pressure than the final test pressures.
Increase the pressure slowly to the strength test pressure and hold it for 15
minutes. Under the Pressure Equipment Regulation this strength test might need
to be witnessed by a notified body.
Safe
– for this test a pressure above the system’s maximum allowable
pressure (PS
i
) is used
Leak tight
– this test is at PS
i
.
The nitrogen used for pressure testing is an asphyxiant, so the area around
the system should be well-ventilated
High pressures are used, so all non-essential personal should be evacuated
from the area
Anyone carrying out the pressure testing should wear safety goggles.
2. Open the cylinder valve
3. Slowly open the regulator
Page
24
1. Ensure the regulator is
closed (wound fully anti
clockwise)
Содержание MOB01-09HFN8-QRD6GW
Страница 1: ...Installation Manual Mission Series R410a Models R32 Models...
Страница 6: ...Page 6 Installation Overview 3 Unit Installation Overview INSTALLATION ORDER...
Страница 8: ...Page 8 Indoor Unit Installation 4...
Страница 10: ...Page 10 Indoor Unit Installation 4...
Страница 14: ...For MOCA02 24HFN1 QRD0GW Page 14 Outdoor Unit Installation Instructions...
Страница 16: ...Drainpipe Installation 6 Page 16...
Страница 39: ...17 Old Park Lane London W1K 1QT Tel 44 0 2074 092009...