MCAC-CTSM-2014-03 DX type water-cooled screw chiller (PCB Control)
79
G= cooling capacity×2.6L
Process type cooling
G= cooling capacity×7.4L
b. In certain occasion (especially in manufacture cooling process), for conforming the system water
content requirement, it’s necessary to mount a tank equipping with a cut-off baffle at the system to
avoid water short-circuit, Please see the following schemes:
Error
Recommendation
Fig.4-4
Error
Recommendation
Error
Recommendation
Fig.4-4
Error
Recommendation
4).Water pipeline installation
Due to the variety of piping practices, it is advisable to follow the recommendations of local
authorities. The installation and insulation of the water pipelines of the air conditioning system shall
be designed and guided by design professionals, and confirm to the corresponding provisions of the
HVAC installation specifications.
Basically, the piping should be designed with a minimum number of bends and changes in elevation
to keep system cost down and performance up.
Chi
ller
con
dens
er
WS
a
c
d e
g
h
j
i
k
Cond return water
Cond outlet water
Cooling
tower
(
Condenser, cooling water hose connection diagrammatic sketch
)
a Flexible connection
k Flow switch
c Butterfly valve
d Pressure gauge
Condenser inlet water
Condenser outlet water
Содержание LSBLG255/MZ
Страница 1: ...LSBLG MZ Model TechnicalServiceManual Water cooled Screw Chiller ...
Страница 15: ...DX type water cooled screw chiller PCB Control MCAC CTSM 2014 03 14 For single head unit LSBLG860 MZ ...
Страница 16: ...MCAC CTSM 2014 03 DX type water cooled screw chiller PCB Control 15 For dual heads unit LSBLG970 1260 MZ ...
Страница 17: ...DX type water cooled screw chiller PCB Control MCAC CTSM 2014 03 16 For dual heads unit LSBLG1490 MZ ...