MCAC-CTSM-2014-03 DX type water-cooled screw chiller (PCB Control)
21
The condenser is equipped with safety valves. And ball valve is connecting safety valve to condenser.
The ball valve maintain full-state, it is closed only when safety valve is opening or replaced.
Ball valve can protect life and property because it can prevent refrigerant from flowing into the air when
safety valve is opening or replaced.
6.2.6 Evaporator
Midea Screw Chiller is equipped with high efficiency shell and tube evaporator that are constructed by
seamless steel tube with anti-corrosive treatment. The evaporator is a direct expansion type with
refrigerant inside the copper tubes and water on the outside. The copper tubes are roll expanded into
carbon steel tube plates.
Constructed with seamless integrally finned copper, the water pipe system makes the evaporator attain
optimal heat exchange efficient. Also they are removable, which makes it available for efficient. Also they
are removable, which makes it available for altering water piping arrangement.
The design working pressure for both evaporator and condenser are 1.0MPa, higher pressure demand
can be customized.
6.2.7 Condenser
Shell and tube operates with refrigerant in shell and water in tubes. Replaceable water tubes are
fabricated from integral finned cooper and mechanically bonded to steel tube sheets. The condenser is
GB151-1999 (Chinese standard) designed, constructed, inspected and stamped. Water side working
pressure is designed for 1.0MPa.
The condenser is used high-efficient tubes to enhance its transfer performance. Meanwhile, the system's
COP can be increased largely by adding the subcooler.
6.2.8 Throttle valve
The chiller is equipped with expansion valve to decompress and expanse refrigerant.
7.Water Flow
Balance the chilled water flow through the evaporator and the condenser water flow through the
condenser. The flow rates must fall between the minimum and maximum values shown in the below
table. Flow rates below the minimum values shown will result in laminar flow which will reduce efficiency,
cause erratic operation of the electronic expansion valve and could cause low temperature cutouts. On
the other hand, flow rates exceeding the maximum values shown can cause erosion on the heat
exchanges water connections and tubes, even piping breaking.
Variable chilled water flow through the heat exchanges while the compressor(s) are operating is not
recommended. The chiller control set points are based upon a constant flow and variable temperature.
Содержание LSBLG255/MZ
Страница 1: ...LSBLG MZ Model TechnicalServiceManual Water cooled Screw Chiller ...
Страница 15: ...DX type water cooled screw chiller PCB Control MCAC CTSM 2014 03 14 For single head unit LSBLG860 MZ ...
Страница 16: ...MCAC CTSM 2014 03 DX type water cooled screw chiller PCB Control 15 For dual heads unit LSBLG970 1260 MZ ...
Страница 17: ...DX type water cooled screw chiller PCB Control MCAC CTSM 2014 03 16 For dual heads unit LSBLG1490 MZ ...