DX type water-cooled screw chiller (PCB Control)
MCAC-CTSM-2014-03
74
Dual compressors parataxis type unit
Any person is not allowed to stand below the unit when sling it.
2).Foundation
①
Please take into account the construction of installation foundation. Attention should be
especially paid to the intensity of the floor and noise elimination when installing the unit in
interlayer or on the top floor. It is suggested to consult the building designer before installation.
②
For convenient drainage, gutter way should be made around the basement to ensure the
drainage unblocked.
③
To eliminate the vibration and noise, put an absorber between the unit and basement and keep
the unit in balance. Install a shockproof foundation when necessary.
④
Vibration isolators are recommended for all roof mounted installations or wherever vibration
transmission is a consideration. Neoprene Isolation is optional, it is recommended for normal
installations and provides good performance in most applications for the least cost. Spring
isolator is level adjustable, spring and cage type isolators for mounting under the unit base rails.
1
” nominal deflection may vary slightly by application.
Typical Isolation:
Anchor Bolt
Chiller Leg
eg
Rubber Pad
Steel Base Plate
Concrete Base
Содержание LSBLG255/MZ
Страница 1: ...LSBLG MZ Model TechnicalServiceManual Water cooled Screw Chiller ...
Страница 15: ...DX type water cooled screw chiller PCB Control MCAC CTSM 2014 03 14 For single head unit LSBLG860 MZ ...
Страница 16: ...MCAC CTSM 2014 03 DX type water cooled screw chiller PCB Control 15 For dual heads unit LSBLG970 1260 MZ ...
Страница 17: ...DX type water cooled screw chiller PCB Control MCAC CTSM 2014 03 16 For dual heads unit LSBLG1490 MZ ...