MCAC-CTSM-2014-03 DX type water-cooled screw chiller (PCB Control)
83
manual type, open the discharge valve of the chilled water pipeline to discharge all air in the
pipeline.
23) Adjust the flow and inspect whether the water pressure drop of the evaporator meets the
requirement of the unit’s normal operation. The pressure at the chilled water inlet and outlet of
the unit shall be kept at least 0.2MPa.
24) The total water quantity in the system should be sufficient to prevent frequent
“on-off” cycling. A
reasonable minimum quantity would allow for a complete water system turnover in not less
than 15 minutes.
3.Wiring installation
WARNING:
In order to prevent any accident of injury and death during the site wiring , the power supply
shall be cut off before the line is connected to the unit.
Wiring must comply with all applicable codes and ordinances. Warranty is voided if wiring is not in
accordance with specifications. An open fuse indicates a short, ground, or overload. Before replacing a
fuse or restarting a compressor , the trouble must be found and corrected.
(1) Copper wire is required for all supply lines in field connection to avoid corrosion and overheat at
the connection of terminals. The lines and control cables shall be separately paved and
equipped with protective pipes to avoid intervention of supply line in control cable.
(2) Power section: It is required to connect the power supply cable to the control cabinet of the unit,
when it arrives at the jobsite. The power supply cable is connected to the terminals of L1, L2, L3,
N and PE and the terminals need to be fixed again after 24h running (the minimum allowed
time). Please seal the entering wiring hole after users installed the main power wires, in order to
avoid the dust entering into electric control cabinet.
Caution: it is suggested that to use appropriate tools to make sure that a enough height to
install the main power wires if the basement is higher than 200 mm. Breaking isolation switches
should be added between the power cord of users and the unit. The capacities of the breaking
isolation switches recommended are see
electrical control .
(3) Attention: refrigerant selection: the previous software settings are replaced by the current
hardware settings to avoid the possibility of improper operation of the software leading to
wrongly selected refrigerant and damage to the unit.
(4) In order to avoid wrong control in field connection, the liquid control circuit (24 V) shall not be in
the same conduit with the lead wire with voltage higher than 24 V.
(5) The control circuits of various units are all 220 V, and for the wiring ways of the control circuits,
please refer to the wiring diagrams supplied along with the units.
(6) A unit consists of master compressor and slave compressor communicating via shield wire
protected by sleeve and paved separate from supply line.
(7) The control output cable to be connected on site shall be AC250V-1mm2, and 0.75mm2 shield
wire (24 V) shall be used for control signal line.
(8) Attentions: Read the electrical wiring principle diagram and connect the wires strictly according
to the wiring terminal diagram. Three-core shield cable (3×0.75mm2) shall be used for the
Содержание LSBLG255/MZ
Страница 1: ...LSBLG MZ Model TechnicalServiceManual Water cooled Screw Chiller ...
Страница 15: ...DX type water cooled screw chiller PCB Control MCAC CTSM 2014 03 14 For single head unit LSBLG860 MZ ...
Страница 16: ...MCAC CTSM 2014 03 DX type water cooled screw chiller PCB Control 15 For dual heads unit LSBLG970 1260 MZ ...
Страница 17: ...DX type water cooled screw chiller PCB Control MCAC CTSM 2014 03 16 For dual heads unit LSBLG1490 MZ ...