MCAC-CTSM-2014-03 DX type water-cooled screw chiller (PCB Control)
89
For later armored dip-type temperature sensor, no lubricating oil is required for heat transfer.
2. Start-up
Before start-up of the unit, the following performance parameters need to be inspected:
(1) High/low voltage value of the system. For the unit shutdown and waterless in a long term, the
liquid and gas of the system shall be equivalent and close to the saturation pressure
corresponding to the current ambient temperature. The correlation of saturation temperatures
and pressures (the pressures in the list are gage pressures, among which, the atmospheric
pressure is 0.1MPa) of R22 and R134a refrigerant is shown in table 1:
In the pressure gauge scale, taking the right figure for example: the values outside of the black
circle are pressure values (unit: bar), and the values of the red, blue and green circles indicate
saturation temperatures of refrigerants R404A, R22 and R134a respectively under the relative
pressure. The types of refrigerants indicated in different pressure gauges might differ.
[Table 1]
If the high/low voltage deviates much from the saturation pressure corresponding to the current
Refrigerant
Temperature
℃
R22 Refrigerant Pressure
(Gage Pressure) MPa
0
0.40
5
0.48
10
0.58
15
0.69
20
0.81
25
0.94
30
1.09
35
1.22
40
1.40
Armored
dip-type
temperature sensor
In shutdown status,
the high and low
voltages shall be the
same and equal to the
saturation
pressure
corresponding to the
current temperature.
Содержание LSBLG255/MZ
Страница 1: ...LSBLG MZ Model TechnicalServiceManual Water cooled Screw Chiller ...
Страница 15: ...DX type water cooled screw chiller PCB Control MCAC CTSM 2014 03 14 For single head unit LSBLG860 MZ ...
Страница 16: ...MCAC CTSM 2014 03 DX type water cooled screw chiller PCB Control 15 For dual heads unit LSBLG970 1260 MZ ...
Страница 17: ...DX type water cooled screw chiller PCB Control MCAC CTSM 2014 03 16 For dual heads unit LSBLG1490 MZ ...