Page 29
UF AV5500 Area-Velocity Flow Meter
OPTIONAL PIPE BAND MOUNTING WITH QZ02L SENSOR
Install the stainless steel pipe band with the sensor mounting
bracket at the invert (bottom) of the pipe. Ensure that the
sensor bracket is parallel to the water surface (check with a
level). Mount so the tapered end of the sensor will point
upstream and the sensor cable will point downstream. (Turn
the ¼” adjustment nut clockwise to expand the bracket and secure to the pipe wall by friction fit.)
Insert the sensor into the mounting bracket and tie-wrap the sensor cable securely to the pipe band using
the holes provided.
OPTIONAL QZ02L-B VELOCITY SENSOR MOUNTING
Mount the velocity sensor at or near the bottom of the channel or pipe in a position where it will be
continuously submerged. The QZ02L-B velocity sensor does not have to be parallel to the water surface.
Position where silt or solids will not build-up on the sensor.