DIAGNOSTICS AND ERROR DESCRIPTIONS
LED DISPLAY
ERROR CODE
ERROR DESCRIPTION / CAUSE
ERROR TYPE
No Color
--
Not powered
No Error
GREEN
Slow Flashing
--
Normal operation: STANDBY
No Error
GREEN
Fast Flashing
--
Normal operation: HEATING
No Error
ORANGE
--
In priming mode
No Error
RED
Flashing
A 0
Water conductivity too low
Blocking/Resolving
RED
Flashing
A 4
Operating temperature too low
Blocking/Resolving
RED
Flashing
A 5
Operating temperature too high
Blocking/Resolving
RED
Flashing
A 6
Outlet water temperature 41°F above
set point
Blocking/Resolving
RED
Flashing
A 7
Inlet cold water input sensor open circuit
Blocking/Resolving
RED
Flashing
A 8
Inlet cold water input sensor short circuit
Blocking/Resolving
RED
Flashing
A 9
Outlet cold water input sensor open circuit
Blocking/Resolving
RED
Flashing
A A
Outlet cold water input sensor short circuit
Blocking/Resolving
RED
Flashing
A 0
AC mains electrical supply failure
Blocking/Resolving
RED
F A
High temperature limit exceeded >158°F
Mechanical Lockout
RED
F b
Water conductivity too high
Mechanical Lockout
RED
F 0
Earth leakage detection
Mechanical Lockout
RED
F d
CPU watch dog timer error
Mechanical Lockout
RED
F E
Temperature controller error
(A6 error more than 5 times in one operation)
Mechanical Lockout
RED
F F
Unknown failure