|      INSTALLATION MANUAL for CFEWH SERIES 6-13      |      V01 - 12 / 02 / 2021

PLUMBING INSTALLATION  

FOR LICENSED PLUMBERS ONLY

The unit is a closed outlet water heater and is intended to operate at the pressure 

of the water mains, where the flow of water is controlled by one or more faucets/

valves in the outlet line.

The unit can be installed into any type of commercial or residential construction 

as per the current plumbing standards.

However, it is mandatory for a water pressure limiting valve and a shutoff 

valve to be connected in series with the unit’s 

6

 Cold Water Inlet Connection.

 ›

The unit maximum rated operating line pressure is 0.8 MPa / 8 bar / 116 PSI. 

 ›

The unit minimum operating pressure is atmospheric pressure. 

 ›

The installation of a pressure limiting valve – a mandatory requirement – 

ensures that excess water pressure applied, as result of water hammer and/

or other circumstances, does not stress the appliance unduly.

 ›

The inlet water pressure limiting valve must be rated at    

 

0.5 MPa / 5.0 bar / 72.5 psi.

 ›

The shutoff valve installed must not be a non-return type valve.

 ›

Inlet and outlet piping must be maximum 3/4�, minimum 20� pipe length.

 ›

If the water heater is supplying a dishwasher/washing machine, a water 

hammer arrestor must be installed on the outlet side of the water heater.

HOT

WATER

OUT

COLD

WATER

IN

PRESSURE

LIMITING

VALVE

5 bar/500 kpa

SHUTOFF

VALVE

INLET

OUTLET

COLD

WATER

IN

PRESSURE

LIMITING

VALVE

5 bar/500 kpa

SHUTOFF

VALVE

MUST NOT BE

A NON-RETURN

TYPE VALVE

INLET

HOT

WATER

OUT

OUTLET

LESS THAN

250mm

SINGLE CFEWH SERIES 6-13 

PLUMBING CONNECTION

TANDEM CFEWH SERIES 6-13

 

x

 

2

 

PLUMBING CONNECTION

 IMPORTANT: 

MicroHeat, nor its Distributors, 

will be liable for any damages 

through failure to comply with 

the installation and operating 

instructions outlined in this 

manual – specifically in this 

instance where the specified 

water pressure limiting valve 

and shutoff valve type, as 

indicated, must be installed 

with this unit.

PAGE 1 of 1

1.  

Switch OFF the circuit breaker and isolation switch supplying the electric 

mains power to the unit for plumbing installation. 

 

2.  

Connect the water pressure limiting valve (5.0 bar / 72.5 psi / 500 kpa) and 

shutoff valve. 

3.  

Connect the water supply via the shutoff valve and pressure limiting valve 

to the unit to the 

6

 Inlet Water Connection. The 

6

 Inlet and 

7

 Outlet 

Water Connections are both ¾� NPT. NOTE: Flush the cold water line before 

connecting to the unit.

4.  

Connect the hot water from the 

7

 Outlet Water Connection. 

5.  

Run water through the unit without power to ensure there are no leaks.

6.  

Switch ON the circuit breaker and isolation switch supplying the electric 

mains power to the unit for plumbing installation.

If the LED is slow flashing 

GREEN

, the unit is in standby mode and is ready for use. 

Turning hot water on will initiate the heating process and hot water should exit from 

of the point-of-use water outlet. The LED will illuminate as fast flashing 

GREEN

See Page 15 for full list of light indicator signals. 

STEPS FOR INSTALLATION

END OF SECTION

Содержание MH 6 Series

Страница 1: ...LOW ELECTRIC WATER HEATER CFEWH SERIES 6 13 SINGLE PHASE USA INSTALLATION OPERATION MANUAL LEARN MORE AT MICROHEAT US INFO OR SCAN CODE NEXT GENERATION MOLECULAR HEAT TECHNOLOGY ON DEMAND FLOW ADVANCE...

Страница 2: ...Dimensions 4 Speci cations 5 Pre Installation Checklist 6 Installation Overview 7 Electrical Installation BY A LICENSED ELECTRICIAN ONLY 8 10 Plumbing Installation BY A LICENSED PLUMBER ONLY 11 Prepar...

Страница 3: ...ES 6 13 Units include displays showing output water temperature settable up to 140 F temperatures below 120 F are recommended to prevent scalding and flow rate Please ensure you read through the Pre I...

Страница 4: ...CFEWH Electrical Supply Optimized Energy Accurate Heated Water Temperature Optimized Tandem Capability Optimized energy is the capacity to heat water more efficiently delivering reductions in the con...

Страница 5: ...drained of water to prevent frozen water damage from occurring Failure to comply with the installation and operating instructions or improper use voids the warranty Here are some suggested options for...

Страница 6: ...atchel Wall Mounting Screws NOT INCLUDED Inlet Filter PCBA Terminal Block Electric Mains Supply Cable Gland RED GREEN LED GREEN Ready RED Error Flow Rate Temperature Setting Display Exterior Cover Plu...

Страница 7: ...Optimized Direct Energy Transfer Full Digitally Controlled Water Heating Nominal Capacity gallons 0 1 gallons 2 x 0 1 gallons STANDARDS Electrical Safety UL 499 Ed 14 EMC FCC IP Rating IP25 HOT WATER...

Страница 8: ...will be liable for any damages due to failure to comply with the installation and operating instructions outlined in this manual or through improper use Improper use includes the use of this unit to h...

Страница 9: ...Once active wires are connected to the unit the unit must be mounted into position and tested for connectivity The unit hot water outlet is connected to a hot water plumbing fixture and the cold wate...

Страница 10: ...s usually more than one Diversity Factor sum of total demands maximum demand on feeder DEMAND FACTOR Demand Factor is the ratio of the sum of the maximum demand of a system or part of a system to the...

Страница 11: ...AINS SUPPLY CABLE GLAND PRINTED CIRCUIT BOARD ASSEMBLY PCBA V7 4 DISPLAY PCBA PLUG LED INDICATOR PCBA RESET BUTTON PCBA TERMINAL BLOCK L1 L2 ELECTRICAL INSTALLATION TANDEM INSTALLATION With tandem ins...

Страница 12: ...imum diameter of 5 16 will damage the mounting base and crack the body VOIDING THE WARRANTY The unit should be mounted onto a solid internal wall or in an internal cupboard or space capable of continu...

Страница 13: ...ITING VALVE 5 bar 500 kpa SHUTOFF VALVE MUST NOT BE A NON RETURN TYPE VALVE INLET HOT WATER OUT OUTLET LESS THAN 250mm SINGLE CFEWH SERIES 6 13 PLUMBING CONNECTION TANDEM CFEWH SERIES 6 13 x 2 PLUMBIN...

Страница 14: ...thout incurring power overshoot Once primed the unit will ramp up to the optimized power required at the time without overshoot NOTE Power overshoot typically results from the maximum power input requ...

Страница 15: ...120 116 113 110 107 105 102 98 96 OPTIMIZED ENERGY USAGE kW 3 1 4 2 5 2 6 3 7 3 8 4 9 4 10 5 11 5 12 6 13 0 13 0 13 0 13 0 13 0 13 0 13 0 13 0 13 0 80 F INPUT WATER TEMPERATURE WARM WATER FLOW RATE gp...

Страница 16: ...The 16 LED indicator on the 10 Exterior Cover indicates the operational status of the unit LED INDICATOR NOT ILLUMINATED No electricity is being supplied to the unit SLOW FLASHING GREEN Standby mode...

Страница 17: ...t point Blocking Resolving RED Flashing A 7 Inlet cold water input sensor open circuit Blocking Resolving RED Flashing A 8 Inlet cold water input sensor short circuit Blocking Resolving RED Flashing A...

Страница 18: ...connect the connecting cable from the 19 PCBA Plug and replace the 10 Exterior Cover MAINTENANCE The unit is designed to provide long and reliable service Actual life expectancy will vary with water q...

Страница 19: ...eat CFEWH literature PROCEDURE FOR HONORING WARRANTY 1 To initiate a claim for a warranty against defects the consumer shall return product to place of purchase for replacement For additional product...

Страница 20: ...ty Ltd 20 Pickering Road Mulgrave VIC 3170 Australia DISTRIBUTED BY JVIS USA LCC 52048 Shelby Parkway Shelby Charter Township MI 48315 Please contact our customer service at support microheat us Micro...

Отзывы: