The appliance must be connected to the mains
supply with fixed wiring.
It is recommended that an appropriate mains
isolation switch be installed in-line with the fixed
wiring electrical supply.
The appliance must be installed on a branch
circuit with a protective device rated at 55 Amps.
Bring the Live / Live / Ground supply through the
15
Electric Mains Supply Cable Gland (OPTION
1) or through the
19
Exterior Cover Hole
(OPTION 2) as shown below.
›
The LIVE wire (1) must be connected to the
L1 terminal.
›
The LIVE wire (2) must be connected to the
L2 terminal.
›
The EARTH wire (
GREEN
/
YELLOW
) must
be connected to the terminal.
15
19
8
14
20
ELECTRIC MAINS
SUPPLY CABLE GLAND
PRINTED CIRCUIT BOARD
ASSEMBLY (PCBA) V7.4
DISPLAY PCBA PLUG
(LED INDICATOR)
PCBA RESET BUTTON
PCBA TERMINAL BLOCK
L1
L2
ELECTRICAL INSTALLATION
TANDEM INSTALLATION
With tandem installations, both units must be fitted with
their own respective circuit breaker and isolation switch.
See page 4 for identification
of other parts of the unit.
FOR LICENSED ELECTRICIANS ONLY
PAGE 2 of 3
STEPS FOR INSTALLATION
1.
Find a clean, flat surface and place the unit on its
back.
Using both your thumbs and forefingers,
grip the
10
Exterior Cover firmly along the bottom
of the unit, and push the cover slowly up to
separate it from the
1
Chassis of the unit.
2.
Carefully remove the
19
Display PCBA/LED Plug
and Cable connecting either the Display PCBA
or Indicator LED on the outside of the
10
Exterior
Cover to the
8
PCBA. Set aside for reconnection
during electrical installation.
15
18
OPTION 1
OPTION 2