| INSTALLATION MANUAL for CFEWH SERIES 6-13 | V01 - 12 / 02 / 2021
OPTIMIZED ENERGY USAGE
The table below shows the flow rate in gallons per minute (gpm), related to deliverable output water temperature (°F)
and optimized electrical energy usage (kW). The table shows you the results that can be achieved by varying the water
flow and temperature. The optimum operational capability of the unit is reached at full-rated power.
53°F INPUT WATER TEMPERATURE
WARM WATER FLOW RATE (gpm)
0.4 0.5 0.7 0.8 0.9
1.1
1.2
1.3
1.5
1.6
1.7
1.8 2.0
2.1 2.2 2.4 2.6 2.9 3.2
OUTPUT WATER TEMP (°F)
122 122 122 122 122 122 122
117
111 106 102
98
95
92
89
87
84
80
78
OPTIMIZED ENERGY USAGE (kW)
4.2 5.6
7.0 8.4 9.8 11.2 12.6 13.0 13.0 13.0 13.0 13.0 13.0 13.0 13.0 13.0 13.0 13.0 13.0
62°F INPUT WATER TEMPERATURE
WARM WATER FLOW RATE (gpm)
0.4 0.5 0.7 0.8 0.9
1.1
1.2
1.3
1.5
1.6
1.7
1.8 2.0
2.1 2.2 2.4 2.6 2.9 3.2
OUTPUT WATER TEMP (°F)
122 122 122 122 122 122 122 122 120
115
111 107 104
101
98
96
93
89
87
OPTIMIZED ENERGY USAGE (kW)
3.7 4.9
6.1
7.3 8.5 9.8 11.0 12.2 13.0 13.0 13.0 13.0 13.0 13.0 13.0 13.0 13.0 13.0 13.0
71°F INPUT WATER TEMPERATURE
WARM WATER FLOW RATE (gpm)
0.4 0.5 0.7 0.8 0.9
1.1
1.2
1.3
1.5
1.6
1.7
1.8 2.0
2.1 2.2 2.4 2.6 2.9 3.2
OUTPUT WATER TEMP (°F)
122 122 122 122 122 122 122 122 122 122 120
116
113
110 107 105 102
98
96
OPTIMIZED ENERGY USAGE (kW)
3.1 4.2 5.2 6.3
7.3 8.4 9.4 10.5 11.5 12.6 13.0 13.0 13.0 13.0 13.0 13.0 13.0 13.0 13.0
80°F INPUT WATER TEMPERATURE
WARM WATER FLOW RATE (gpm)
0.4 0.5 0.7 0.8 0.9
1.1
1.2
1.3
1.5
1.6
1.7
1.8 2.0
2.1 2.2 2.4 2.6 2.9 3.2
OUTPUT WATER TEMP (°F)
122 122 122 122 122 122 122 122 122 122 122 122 122
119
116
114
111 107 105
OPTIMIZED ENERGY USAGE (kW)
2.6 3.5 4.4 5.2
6.1
7.0
7.9
8.7 9.6 10.5 11.3 12.2 13.0 13.0 13.0 13.0 13.0 13.0 13.0
89°F INPUT WATER TEMPERATURE
WARM WATER FLOW RATE (gpm)
0.4 0.5 0.7 0.8 0.9
1.1
1.2
1.3
1.5
1.6
1.7
1.8 2.0
2.1 2.2 2.4 2.6 2.9 3.2
OUTPUT WATER TEMP (°F)
122 122 122 122 122 122 122 122 122 122 122 122 122 122 122 122 120
116
114
OPTIMIZED ENERGY USAGE (kW)
2.1 2.8 3.5 4.2 4.9 5.6 6.3
7.0
7.7 8.4
9.1 9.8 10.5 11.2 11.9 12.6 13.0 13.0 13.0
98°F INPUT WATER TEMPERATURE
WARM WATER FLOW RATE (gpm)
0.4 0.5 0.7 0.8 0.9
1.1
1.2
1.3
1.5
1.6
1.7
1.8 2.0
2.1 2.2 2.4 2.6 2.9 3.2
OUTPUT WATER TEMP (°F)
122 122 122 122 122 122 122 122 122 122 122 122 122 122 122 122 122 122 122
OPTIMIZED ENERGY USAGE (kW)
1.6
2.1 2.6
3.1
3.7 4.2 4.7 5.2 5.8 6.3 6.8
7.3
7.9 8.4 8.9 9.4 10.5 11.5 12.6
107°F INPUT WATER TEMPERATURE
WARM WATER FLOW RATE (gpm)
0.4 0.5 0.7 0.8 0.9
1.1
1.2
1.3
1.5
1.6
1.7
1.8 2.0
2.1 2.2 2.4 2.6 2.9 3.2
OUTPUT WATER TEMP (°F)
122 122 122 122 122 122 122 122 122 122 122 122 122 122 122 122 122 122 122
OPTIMIZED ENERGY USAGE (kW)
1.0
1.4
1.7
2.1 2.4 2.8
3.1 3.5 3.8 4.2 4.5 4.9 5.2 5.6 5.9 6.3
7.0
7.7 8.4