52
MicroEngine
®
XP-GT/GTR Programming Manual
v4.00
5.2.2 Output Type
This menu lets users specify the output type; whether the output connected is a
constant-on alarm or a pulsing-on alarm.
To specify the output type, please follow steps below:
1. Enter Configuration Menu.
2. Press
5
for
Alarm Menu
.
3. Press
2
for
Output Setting
.
4. Press
2
for
Output Type
. Screen as below will be shown. Enter from
1
to
4
to
select the alarm output. Press
#
to confirm and proceed to set the output type.
Press
↑
or
↓
to toggle the output to be constantly activated,
[CONST]
; or
pulse activated,
[PULSE]
.
Output Type
Switch Output No.[?]
(Min=01, Max=04)
Type [Conts][0000]s
√
- OK
X – Cancel
5. In the section to the right, enter from “0000”
and “3599” in seconds to specify
the duration to activate the output alarm. Press
√
to save changes.
5.2.3 Event Type
This menu lets users specify the event type to trigger the output alarm.
To specify the event type, please follow steps below:
1. Enter Configuration Menu.
2. Press
5
for
Alarm Menu
.
3. Press
2
for
Output Setting
.
4. Press
3
for
Event Type
. Screen as below will be shown. Enter from
1
to
4
to
select the alarm output. Press
#
to confirm and proceed to set the Event
Type.
Event Type
Switch Output No.[?]
(Min=01, Max=04)
Event No.[00] :[/]
√
- OK
X - Cancel
5. Users can select up to 20 events from a total of 62 different events (refer to
Table 1, page 29) to activate the output. Enter between “00” to “19” to select
the event number, and press
↑
or
↓
to specify an event according to event
code provided in Table 1. Press
√
to save changes.