XP-GT/GTR Programming Manual
v4.00
xix.
Fire Release
Description
: Fire Release Enable selection. Once enabled,
the controller will release the door lock when the fire
alarm signal is detected.
Value
: NO, YES.
Default value
: NO.
CAUTION:-
Fire alarm signal must be a normally open dry contact (without
voltage source). To convert wet contact to dry contact, refer to
Appendix 13 and 14.
xx.
Double Leaf
Description
: Double Leaf Enable selection. Once enabled
both door leafs can be opened anytime within the lock
release time. If disabled, the both leafs must be
opened at the same time, otherwise one leaf will be
locked once the other leaf is opened.
Value
: NO, YES.
Default value
: NO.
xxi.
Reader Type
Description
:
Reader Type selection. Users can choose one of four
reader types
[WG] – Wiegand reader
[AB] – ABA reader
[A10] – A10 reader
[RS] – RS485 reader (Plato)
Value
: WG, AB, A10, RS.
Default value
: AB.
NOTE:-
Sub-menu xxi. is only available to GT/GTR (1500L, 3500L, 1500ABL,
3500ABL) series only.
xxii.
FP Autoscan
Description
: Fingerprint Autoscan enable selection. Once enabled,
the fingerprint reader unit will always be scanning for
valid fingerprint to grant door access.
Value
: NO, YES.
Default value
: NO.
NOTE:-
Sub-menu xxii. is only available to GT (3500L, 3500ABL) series only.