XP-GT/GTR Programming Manual
v4.00
xiii.
As Exit Reader
Description
: Built-in Reader enabled or disabled. Once enabled,
controller’s built-in reader is used as exit reader while
external reader is configured to be the entry reader.
Value
: ON, OFF.
Default value
: OFF.
xiv.
Exit Time Zone Enable
Description
: Exit Reader Time Zone Enable selection. Once
enabled, controller will enforce exit access according
to the pre-set user’s Time Zone. In the default setting,
the exit reader will always grant exit access even
though the user’s Time Zone is incorrect.
Value
: ON, OFF.
Default value
: OFF.
xv.
Sounder Period
Description
: Duration for the sounder to activate (in seconds)
when the sounder is triggered.
Value
: 00-99.
Default value
: 00.
NOTE:-
Sub-menu xv. is only available to all GTR (1200, 3000, 1200L, 3000L,
1500L, 1500ABL) series only.
xvi.
GP Output Mode
Description
: GP Output Mode selection. Users can choose
one of three modes to trigger the output system.
[00] –Trigger by GP Output TZ
(refer next menu)
[01] –Trigger by Sounder Setting
(refer section 1.8)
[02] –Trigger by O/P Trigger Event
(refer section 1.9)
Value :
00-02.
Default value
: 00.
xvii.
GP Output Tz
Description
: Time Zone setting for output activation. This will
determine the day of the week and the time of the
day where the output will be enabled.
Value
: 00-50.
Default value
: 00.
(GP Output disabled)
xviii.
GP Output Period
Description
: Duration for the output to activate (in seconds)
when the output is triggered.
Value
: 00-99.
Default value
: 00.
NOTE:-
Sub-menus xvi., xvii., and xviii. are only available to GT (1200, 3200,
1200L, 3200L) series only.