Plumbing Guidelines
General
In order for your sprayer to function properly, it must be
correctly plumbed. The system diagram (See Illustration 33)
at the center of this book shows the plumbing configuration
that works best with the MT-2400 Sprayer Controller. This
section will explain the purpose of each component, list
some problems it can cause and recommend some possible
solutions to those problems.
A WORD ABOUT PRESSURE DROPS
All hose, valves and fittings (especially elbows) cause
undesirable pressure losses. Keep hoses as large as practical.
Don’t use longer hoses than necessary. Avoid bends whenever
possible. Use as few fittings as possible. Use full port valves
or the next larger size valve. Long hoses should be supported
to avoid sagging and kinking. Many spray tip manufacturers
have charts showing pressure drop for various fittings and
hose sizes.
Now let’s break the system diagram into five sections and
cover each one separately. The five sections are the pump
inlet line, the agitation line, the flowmeter (boom) line, the
servo line and the pump itself.
PUMP INLET
The hose connecting the tank to the pump should be at
least as large as the pump inlet port. In most cases 11/4” is a
good size. The valve in this line is for complete tank shut-off
only and should always be fully open during operation. If
this hose is too small or the valve is partially closed, you may
not be able to reach your high end goals and pump damage
could occur.
AGITATION
The size of the agitation line is dependent upon the amount
of agitation required which is determined by the size of the
tank and the type of chemical being used. In most cases a 1”
hose is large enough.
SERVO
On the system diagram, the hose between tee “B” and the
servo can usually be 3/4” but 1” will also work. The hose
between the servo and tee “C” should be at least as large as
the servo. If these lines are too small, you may experience
little or no pressure adjustment.
FLOWMETER
The line feeding the flowmeter and the boom shut-off valves
should be at least as large as the flowmeter. The size of
lines going from the shut-off valves to each boom section
depends on the flow rate of each boom.
44
PUMP
The pump must have enough capacity to satisfy the agitation,
servo and flowmeter sections of the plumbing. To determine
if your pump is large enough you must add up the gallons
per minute of all three sections. The following example will
take you through the steps involved.
EXAMPLE
Let’s say our example sprayer has a 300-gallon tank
with a Spraying Systems 6290 SC-8 Jet Agitator.
The
agitator uses 10.2 GPM at 40 PSI. (Spraying Systems
Catalog 38, page 44).
The sprayer has a 40’, three-section boom. Each section
is 160” with four tips at 40” for a total of 12 tips. We
plan to put on a 25 GPA at 5 MPH and in some areas
of the fields we may want to use the Delta feature
and increase our rate to 30 GPA and in other areas
decrease to 15 GPA. After checking the tip charts we
find that a TK-5 Floodjet has a range of 14.9 to 30 GPA
at 5 MPH. According to the charts, to get 30 GPA at 5
MPH with a TK-5, the pressure must be 40 PSI. At 40 PSI
a TK-5 will spray 1.0 GPM. So, 12 tips at 1.0 GPM each
is a total of 12 GPM.
Now let’s add everything together.
Agitation
10.2
Spray tips
12.0
Servo
5.0
27.2
Total
GPM
The above addition shows that the system needs 27.2
GPM at 40 PSI. If we add a 10% margin (27.2 x 1 = 2.72
and 27.2 = 29.92), we have about 30 GPM. To be sure
we have enough volume, the pump should be able to
deliver 30 GPM or more at 40 PSI.
Содержание MT-2400 LR
Страница 1: ...REFERENCE MANUAL AUTOMATIC RATE CONTROLLER MT 2400 TM LR...
Страница 46: ...Appendices 46...