Designer Series Direct Vent Gas Fireplace

VeNTING INSTaLLaTIoN 

INSTaLLaTIoN PLaNNING 

There are two basic types of direct-vent installation:

 

   Horizontal Termination

 

   Vertical Termination

It is important to select the proper length of vent pipe for the 
type of termination you choose. It is also important to note the wall thickness. 

FoR hoRIZoNTaL TeRMINaTIoN

Select the amount of vertical rise desired. All horizontal run of venting must have 1/4" rise for every 12" 
of run towards the termination below 7

Z\x

' of vertical rise from floor of fireplace. With 7

Z\x

 feet or more 

of vertical rise from the floor of the fireplace, the horizontal run may be level. NEVER run vent piping 
down.
You may use up to three 90° elbows in this vent configuration. Refer to Vertical/Horizontal Termination 
Configurations on Page 21.

FoR VeRTICaL TeRMINaTIoN

Measure the distance from the fireplace floor to the ceiling. Add the ceiling thickness, the vertical rise in 
an attic or second story, and allow for sufficient vent height above the roof line. 

NOTE: You may use two 45° elbows in place of a 90° elbow. You must follow rise to run ratios 
when using 45° elbows. The appliance is approved for use with three 90° elbows maximum or a 
combination of  90° and 45° elbows up to a maximum of 270°. 

For two-story applications, firestops are required at each floor level. If an offset is needed in the attic, 
additional pipe and elbows will be required.
You may use a chase with a vent termination with exposed pipe on the exterior of the house. See 

Install-

ing Vent System in a Chase

 below. If pipe is enclosed in chase, it is not exposed. 

It is very important that the venting system maintain its balance between the combustion air intake and 
the flue gas exhaust. Certain limitations apply to vent configurations and must be strictly followed.

INSTaLLING a VeNT SySTeM IN aN ouTSIDe ChaSe

A chase is a vertical boxlike structure built to enclose venting that runs along the outside of a building. 
A chase is required for such venting. 

N

o

TIC

e

when installing in a chase, you should insulate the chase as you would the 
outside walls of your home. This is especially important in cold climates. 
Insulation should be considered a combustible material. Maintain proper 
clearances to all combustible materials. 

w

a

RNING

always  maintain  minimum  clearances  around  vent  systems.  The  minimum  clearances  to 
combustibles for horizontal vent pipe are 3" at the top* and 1" at the sides and bottom of the vent 
system until the pipe penetrates the nearest vertical wall (1" required). a 1" minimum clearance 
all around the pipe must be maintained at outside wall and on vertical runs. Do not pack the 
open air spaces with insulation or other materials. This could cause high temperatures and may 
present a fire hazard. 
*unless the vertical run is 7

Z\x

 feet or higher from floor of fireplace, the clearance for the horizontal 

run is 1" on all sides.

Treatment  of  firestops  and  construction  of  the  chase  may  vary  from 
building type to building type. These instructions are not substitutes for 
the requirements of local building codes. you must follow all local building 
codes. 

N

o

TIC

e

Never  run  the  vent  pipe  down.  This  may 
cause excessive temperatures which could 
cause a fire. 

w

a

RNING

Содержание CLLDVNS

Страница 1: ...nstaller service agency or the gas supplier This appliance may be installed in an aftermarket permanently located manufactured home USA only or mobile home where not prohibited by local codes This app...

Страница 2: ...34 Command Center Wall Installation 34 Wall Switch Installation 34 Signature Command Wiring Diagram 35 Optional Fan Blower Systems 36 Signature Command Single Blower BLOTSTSC 36 Automatic Dual Thermos...

Страница 3: ...tions for future reference IMPORTANT SAFETY INFORMATION This fireplace is a vented product This fireplace must be properly installed by a qualified service person The glass door must be properly seate...

Страница 4: ...replace with glass door removed cracked or broken Code Approval Direct Vent type appliances draw all combustion air from outside of the dwelling through the vent pipe These appliances have been tested...

Страница 5: ...are certified without deration for elevations up to 4 500 feet 1 370 m above sea level For elevations above 4 500 feet 1 370 m in USA installations must be in accordance with the current ANSI Z223 1...

Страница 6: ...962 mm 23 584 mm 35 6QE 903 mm 2856M 718 mm 25 6M 654 mm 3356QE 840 mm 1 4 6 mm 3 6M 95 mm 24 610 mm 27 6M 705 mm 46 6 1178 mm 38 6QE 979 mm 7 6 200 mm FP2852 LDV corner dims 12 305 mm 47 6 1216 mm 41...

Страница 7: ...mm 2856M 718 mm 25 6M 654 mm 7 6 200 mm 556 130 mm 156 29 mm 1 4 6 mm 1 4 6 mm 3356QE 840 mm 38 6QE 979 mm 46 6 1178 mm 7 6 200 mm 12 305 mm 47 6 1216 mm 41 6 1064 mm 37 6 962 mm 23 584 mm Fp2853 LDV...

Страница 8: ...rds Figure 5 STLDV See thru Framing If using 5 8 drywall remove drywall supports rotate 180 and reinstall The fireplace must be secured to the floor and or to framing studs as shown in Figure 5 Use fo...

Страница 9: ...t of holes positioned slightly inwards If using 5 8 drywall remove framing tabs and re install on 2nd set of holes positioned slightly inwards If using 5 8 drywall remove drywall supports rotate 180 a...

Страница 10: ...0 and reinstall Figure 7 PFDV Peninsula Framing If using 5 8 drywall remove framing tabs and re install on 2nd set of holes positioned slightly inwards The fireplace must be secured to the floor and o...

Страница 11: ...e chase cavity between the studs and under the floor on which the appliance rests if the floor is above ground level firebox framing Firebox framing can be built before or after the appliance is set i...

Страница 12: ...nd draperies due to heat from appliance Never obstruct the front opening of the fireplace Do not install in the vicinity where gasoline or other flammable liquids may be stored Vent pipe routing See V...

Страница 13: ...earance mantel clearances NOTE The combustible area above the facing must not protrude more than 1 2 from the facing If it does it is considered a mantel and must meet the mantel requirements listed i...

Страница 14: ...s Read all instructions completely and thoroughly before attempting installation Failure to do so could result in serious injury property damage or loss of life Operation of improperly installed and m...

Страница 15: ...back of the intake box and remove the pipe and gasket Figure 13 5 Replace the flue pipe to top of firebox Ensure the gasket is in place and undamaged Secure with six 6 screws Figure 14 6 Place the fl...

Страница 16: ...wall A minimum 1 clearance to combustibles permitted all around flue at outside wall FP2819 WARNING Horizontal sections of this vent system require a minimum of 3 clearances to combustibles at the top...

Страница 17: ...ouse See Install ing Vent System in a Chase below If pipe is enclosed in chase it is not exposed It is very important that the venting system maintain its balance between the combustion air intake and...

Страница 18: ...e combustion air inlet to any BTU h 3kW 12 30 cm for 10 000 BTU h 3kW 9 other appliances appliances 10 000 BTU h 3kW and 23 cm for appliances 10 000 100 000 Btuh 30kW 36 91 cm BTU h 3kW and 50 000 BTU...

Страница 19: ...sions of the vent system 1 Determine the height of the center of the horizontal vent pipe exiting through the outer wall Using this dimen sion on the Sidewall Vent Graph below locate the point interse...

Страница 20: ...opening in the wall For com bustible walls first frame in opening Combustible Interior Walls Cut a 121 2 x 101 2 hole through the interior wall Combustible Exterior Walls Cut a 101 2 x 101 2 square h...

Страница 21: ...Figure 22 Install Horizontal Termination HOT FP1955 horizontal vent cap Cut Vinyl Siding Away to Fit Standoff Standoff 1250 or 5DT VS Not required for MHSC termination Termination Bolt Wood Screw Nut...

Страница 22: ...of the Transition Elbow to the face of the finished outside wall or the mounting flange of the termination The maximum number of 90 elbows per side wall installation is three 3 Figure 25 If a 90 elbo...

Страница 23: ...hole through the exterior wall frame Figure 25 Noncombustible Walls Hole opening should be 8Z x 216 mm in diameter 2 The center of the hole should line up with the center line of the horizontal rigid...

Страница 24: ...stalling a snorkel a minimum 24 vertical rise is nec essary The maximum horizontal run with the 24 vertical pipe is 36 This measurement is taken from the collar of the fireplace or transition elbow to...

Страница 25: ...e and 1 clearance at the sides and bottom until the flue penetrates the outside wall A minimum 1 clearance all around the flue is acceptable at this point of penetration Unless the vertical run is 7Z...

Страница 26: ...le at this point FP1969 offset w wallstrap Figure 37 Offset with Wall Strap and 45 Elbows Roof Flashing Wall Strap 45 Elbows Ceiling Firstop FP1669 flat ceiling installation 1 Cut a 10Z x 267 mm squar...

Страница 27: ...this purpose Refer to Page 26 Figure 37 Whenever possible use 45 elbows instead of 90 elbows The 45 elbow offers less restriction to the flow of the flue gases and intake air 5 Place the flashing ove...

Страница 28: ...e inner flexible vent pipe and push out of the way 3 Pull and extend the inner flexible vent 4 Slide the inner vent onto the adapter collar for a minimum 1C v overlap 5 Locate the clamp at approximate...

Страница 29: ...ct the 8 flexible vent to the termination ring as in Figure 45 3 Review Figure 45 for proper overlap and clamp placement 4 Three each self penetrating screws are drilled opposite one another and below...

Страница 30: ...bove gear clamp 4 x 7 Rigid Pipe Length Flex to Pipe Adapter DVFFA 8 Gear Clamp 1C v Flexible Pipe and Adapter Outer Collar Overlap UL1777 Flex Vent Figure 48 Typical Pipe Connection Gear Clamp FP1976...

Страница 31: ...l codes not provided A CSA design certified equipment shutoff valve with 1 8 NPT tap is an acceptable alternative to test gauge connection Purchase the CSA design certified equipment shutoff valve fro...

Страница 32: ...recommend that you install a sediment trap drip leg in supply line as shown in Figure 51 Locate sediment trap drip leg where it is within reach for cleaning Install in piping system between fuel supp...

Страница 33: ...rical Wiring WARNING Electrical connections should only be performed by a qualified licensed electrician Main power must be off when connecting to main electrical power supply or performing service Al...

Страница 34: ...all Do not extend beyond the 15 ft wire cable provided If a longer distance is required the 15 ft may be extended up to 30 ft maximum by using two 2 SCSWEK cables plugged together Route the wire from...

Страница 35: ...Black Optional Aux Green Plug in Connector Connector Pin To Control Board Input 300 Watt Max Each Optional A C Module Replaces 6V Adapter When Used 6V AC Adapter Control Board RF Receiver ON OFF Butto...

Страница 36: ...nections should only be performed by a qualified licensed electrician Main power supply must be turned off before connecting the fan to the main electrical power supply or performing service BLOTSTSC...

Страница 37: ...Figure 56 BLOTBLDV Blower Wiring Diagram FP2685 Before installing the blower wire the receptacle into an electrical circuit This should be done before framing the fireplace Wire with minimum 60 C wire...

Страница 38: ...en reinstalling clamps keep fingers clear Figure 58 Remove Glass Frame FP2840 Glass Frame Removal 1 Remove access panel by lifting up and out 2 Release two clamps 500 model has three clamps on bottom...

Страница 39: ...e embers over the burner slots To better enable the gas to permeate the rock wool apply the rock wool in light dime size fluffy pieces WARNING Do not use the entire bag of rock wool to cover the burne...

Страница 40: ...vided making sure to fit the notches in the bottom of the log over the sides of the grate so that it sits firmly in place The log will rest on the grate bar about 1 4 over the top of the burner surfac...

Страница 41: ...surrounding the burner and supporting the grate just outside of the grate The base of the log should be about 1 from the end of log 2 Figure 62 Log 3 LG967 Log 4 LG968 Figure 62 Figure 63 False Bottom...

Страница 42: ...place LG969 Designer DV log 5 log placement 5 Place log 5 on the key provided on log 4 Rest the other end of the log on the false bottom hearth just outside of the grate It should be almost touching t...

Страница 43: ...the gas supplier s instructions If you cannot reach your gas supplier call the fire department C Use only your finger to push in the master switch Never use tools If the switch will not func tion by...

Страница 44: ...r If you smell gas STOP Follow B in the safety information on Page 43 If you do not smell gas go to next step 4 Press the master switch to the ON position Within eight 8 seconds it will beep once This...

Страница 45: ...X X X X X Child Proof Lock out X X X X X LCD Backlight X X X X X Security Codes 16 X X X X X Countdown 6 hr Timer X X X Standard Thermostatic Control Mode X X X Smart Mode Thermostat Auto Flame Blower...

Страница 46: ...o depress button One beep for RF receiver ON or two beeps for RF receiver OFF will be given as confirmation Refer to Figure 57 for location 2 After the RF receiver is on holding the OFF button on the...

Страница 47: ...maximum flame height 2 Press the OFF button to decrease flame height The first two presses will decrease the flame height to medium and low 3 The third press on OFF will turn off the main burner In st...

Страница 48: ...ot and Control Compart ment Keep the control compartment logs and burner areas surrounding the logs clean by vacuuming or brushing at least twice a year Make sure the burner porting pilot air opening...

Страница 49: ...materials may be used Handle glass door with care to avoid striking or scratching it on hard objects To clean glass door follow Glass Removal procedure outlined in the Final Installation section Film...

Страница 50: ...o through Battery polarity wrong LED on the Command Center does not show solid green The 5 pin connector on the AC board broken or bent AC plug is plugged to AC mains Battery voltage low Using battery...

Страница 51: ...PF CR CL Item Description Qty Qty Qty Designer LDV 1 Glass Frame Assembly 2 2 1 20302401 2 Access Panel 2 2 1 20302126 3 Glass Frame Assembly Short 1 1 20302151 4 Access Panel Short 1 1 20302127 5 Gra...

Страница 52: ...52 20302381 Designer Series Direct Vent Gas Fireplace REPLACEMENT PARTS SIGNATURE COMMAND SYSTEM 1 12 2 3 4 15 13 7 16 11 5 9 6 8 2381 LDV SCS burner parts...

Страница 53: ...18 w Shutoff Valve 1 69D0030 69D0030 12 Pilot SCS 1 80D0006 13 Grommet 1 73D0189 73D0189 14 Sealant 1 28D0149 28D0149 15 Control Board SCS 1 80D0018 80D0019 16 Command Center SCS 1 80D0005 80D0005 17...

Страница 54: ...r Series Direct Vent Gas Fireplace REPLACEMENT PARTS Item Description Qty Designer LDV 1 Log 1 1 20302432 2 Log 2 1 20302433 3 Log 3 1 20302434 4 Log 4 1 20302435 5 Log 5 1 20302436 logs 2381 Designer...

Страница 55: ...RICK 2381 LDV brick parts 1 2 3 4 Herringbone Brick Traditional Brick Ref Description Cottage Red Olde English Vintage Brown 1 End Wall Traditional 20302517 2 Long Wall Traditional 20302518 3 End Wall...

Страница 56: ...56 20302381 Designer Series Direct Vent Gas Fireplace VENT components REPLACEMENT PARTS HOT 1 2 3 4 5 6 9 7 8 11 10 0004 MLDV vent parts...

Страница 57: ...908 4DT 06 3 6 9 Pipe Length galvanized 46DVA 09 907 4DT 09 3 6 12 Pipe Length galvanized 46DVA 12 906 4DT 1 3 6 24 Pipe Length galvanized 46DVA 24 904 4DT 4 3 6 36 Pipe Length galvanized 46DVA 36 903...

Страница 58: ...Firestop BHRST 8 2 1 Vertical Termination 58DVA VC 1280 5DT VC 3 4 6 Pipe Length 58DVA 06 1208 5DT 06 3 4 9 Pipe Length 58DVA 09 1207 5DT 09 3 4 12 Pipe Length 58DVA 12 1206 5DT 12 3 4 24 Pipe Length...

Страница 59: ...djustable Vent Length 7TDVP1218 35 64 Adjustable Vent Length 7TDVP3564 8 Vent Pipe 4 pack 7TDVP8 4 12 Vent Pipe 4 pack 7TDVP12 4 24 Vent Pipe 4 pack 7TDVP24 4 36 Vent Pipe 7TDVP36 36 Vent Pipe 30 pack...

Страница 60: ...nt Pipe 7TDVP36 36 Vent Pipe 30 pack 7TDVP36 30 48 Vent Pipe 7TDVP48 48 Vent Pipe 30 pack 7TDVP48 30 5 x 8 to 4 x 7 Adapter 7TDVP58 Flex Adapter Starter Kit DVFFA 8 Twist Lock Elbows 45 Elbow for Vert...

Страница 61: ...20302381 61 Designer Series Direct Vent Gas Fireplace...

Страница 62: ...ed in accordance with the above provisions shall comply with NFPA 720 and ANSI UL 2034 listed and IAS certified Signage A metal or plastic identification plate shall be permanently mounted to the exte...

Страница 63: ...mited Lifetime Warranty will also be void if the appliance is not operated and maintained according to the operating instructions supplied with the appliance and does not extend to 1 firebox burner as...

Страница 64: ...0361 www mhsc com Based on CSA P 4 1 09 Based on CSA P 4 1 09 Recherchez dans la brochure les caract ristique de rendement nerg tique de foyer au gaz nerguide Selon CSA P 4 1 09 Efficiency Ratings Mod...

Отзывы: