2. Installation
Three phases input
This type of connection must be carried out by qualified electrical personnel
Common sources
Separate sources
1 - Remove the one-phase metal strap (1)
2 - Be sure that the metal jumper (2) is
installed
3 - Connect the 5 cables to the normal AC
source terminal block
4 - Connect the 3 cables to the output
terminal block
5 - Remove cover and put input selection
selector
(3)
to three phase position.
1 - Remove the one-phase metal strap (1)
2 - Remove the metal jumper (2)
3 - Connect the 5 cables to the normal AC
source terminal block
4 - Connect the 3 cables to the bypass AC
source terminal block
5 - Connect the 3 cables to the output
terminal block
5 - Remove cover and put single phase or
three-phase switch selection
(3)
to three-
phase position.