34008486EN/AA
- Page 42
7. Maintenance
7.4 Normal position (online mode)
This operation must be carried out by qualified electrical personnel only.
Return to normal position from service position (bypass position).
1 - Push the red padlock in the center of the
manual bypass switch
(1)
to unlock it
2 - Set the bypass switch
(1)
to test position.
3 - Turn on the Normal AC source input
switch
(2)
4 - Set the bypass switch
(1)
to normal
position.
1 - Press and hold the (I) (ON) button
(3)
for
3 seconds.
Pulsar MX Frame performs an internal test
sequence.
LED
(4)
is ON, LEDs
(5)
,
(6)
are green
The load is protected
2
1
TEST
BYPASS
NORMAL
2
TEST
BYPASS
NORMAL
1
TEST
BYPASS
NORMAL
4
3
ESC
I
O
3
4
5
6