34008486EN/AA
- Page 15
2. Installation
2.3 Mounting sub-modules
A dangerous voltage is present inside the power module and the battery module. Any operations to be carried out
on these modules must be done by qualified staff.
You must mount the modules from the lowest level to the highest level.
All the sub-modules must be mounted.
Always keep 150 mm free space behind
the UPS rear panel.
1 - Remove the 6 fixing screws to free the
front panel as shown.
Modules must be mounted from the
lowest level (1) to the highest level (4).
2 - Remove the 4 fixing screws of the
mounting screws to free the power sub-
module space.
Repeat the operation 2 for the battery sub-
module space.
3 - Insert the power sub-module and attach
the 4 mounting screws on each side of the
power sub-module
Caution! the battery is heavy:
approx. 30 kg/65 lbs
4 - Insert the battery sub-module and attach
the 4 mounting screws on each side of the
battery sub-module.
5 - Reattach the front panel
◗
Caution: a battery can cause electrocution and high short circuit currents.
Do not dispose of batteries in a fire. The battery may explode
Do no open or mutilate batteries. Released electrolyte is harmful to the skin and eyes. It may be toxic.