This section describes the messages which may appear on
the alphanumeric display during a fault or alarm on the
Comet. The following brief descriptions indicate whether the
message is informational or an alarm, the meaning of the
message and if any measures may be taken to correct the
fault.
Any state other than normal operation (green “Load
Protected” LED on) is considered a fault by the diagnostics
system.
Before undertaking any servicing or other action, note the
status of the different LEDs and the alphanumeric messages
displayed on the diagnostics panel. If the "Monitor Plus"
option is installed, the same list of messages also appear on
the screen.
If an alarm is present and the load still functions, it is supplied
via the "Static Switch", i.e. it is not protected.
Fault: This message is displayed if a major fault occurs
and results in the Inverter shutting down. The cause of the
fault is given in the secondary alarm message.
This message indicates that the Inverter is on battery power
and the threshold for low battery shutdown warning has
been reached.
Action: Save files quickly before the actual end of battery
backup time.
Fault: This message indicates a fault in the charger module.
Action: Call the Customer Support Services.
Fault: This message indicates that the communications
between the front panel display and controls and the Comet
have been interrupted.
Action: check the connection between the front panel
display and controls and the Comet, and if necessary, call
Customer Support Services.
Fault: This message indicates a general communications
problem between the front panel display and controls and
the Comet.
Action: Call the Customer Support Services.
Fault: This message indicates a fault in the Rectifier
module.
Action: Call the Customer Support Services.
RECTIFIER FAULT
CALL SUPPORT DEPT.
INTERNAL COMMS FAULT
CALL SUPPORT DEPT.
COMMUNICATIONS FAULT
DISPLAY MONITOR
CHARGER FAULT
CALL SUPPORT DEPT
LOW BATTERY
SHUTDOWN IMMINENT
ALARM
3.6.2
Fault List
3 — 16
Operation
86-160310-00
Comet 40 - 150 kVA Uninterruptible Power System
Содержание Comet 100 kVA
Страница 1: ...COMET 40 150 kVA Uninterruptible Power System Installation and User s Manual...
Страница 10: ...this page left blank intentionally x 86 160310 00 Comet 40 150 kVA Uninterruptible Power System...
Страница 28: ...this page left blank intentionally 1 18 Introduction 86 160310 00 Comet 40 150 kVA Uninterruptible Power System...
Страница 35: ...Figure UPS input output connections 100 150kVA 2 3 86 160310 00 2 7 Installation Installation and Users Manual...
Страница 36: ...This page left blank intentionally 2 8 Installation 86 160310 00 Comet 40 150 kVA Uninterruptible Power System...
Страница 62: ...this page left blank intentionally 86 160310 00 Comet 40 150 kVA Uninterruptible Power System...
Страница 64: ......
Страница 65: ......
Страница 66: ...Nothing will stop you now 1660 Scenic Avenue Costa Mesa California 92626 714 557 1636 www mgeups com...