The following is a description of the Comet UPS major
internal components. Refer to the single-line diagram
provided in Figures 1-2, 1-3 and the internal component
views provided in Figures 1-4, 1-5, 1-6, 1-7 and 1-8.
The Rectifier converts the AC input voltage from the utility
source into a DC voltage, supplying the Inverter.
The Inverter converts the DC voltage supplied from either the
Rectifier or the battery system into a three-phase AC voltage.
An AC output filter is used to achieve a computer-grade
sinewave output voltage waveform, with a total harmonic
distortion of less than 2% under linear-load conditions.
The Static Switch transfers the load between the Inverter
output and the bypass AC source without interrupting the
supply of power to the load, allowing the load to continue
operation in the event of a UPS fault. The Static Switch
circuit assures that voltage from the UPS output cannot be
fed back to the utility input lines.
The battery system stores energy for use by the Inverter. The
stored energy is utilized in the event that the AC input power
from the utility source fails, or falls outside of acceptable
tolerances. The internal Battery Charger maintains the
charge of the battery system. The DC output voltage of the
charger is temperature regulated to ensure an optimal
charge voltage. If a customer supplied battery system is to
be used, an external battery charger may be necessary.
The standard battery system is housed in a separate enclo-
sure. For systems where additional back-up time is required,
up to two (2) additional battery cabinets are available.
An external battery system can also be supplied by the
customer.
The communication connectors located behind the front door
of Comet supply the following information:
1.3.5
Communication
Interface
1.3.4
Battery System
1.3.3
Static Switch
1.3.2
Inverter
1.3.1
Rectifier
1.3
Description of
Major Internal
Components
Comet 40 - 150 kVA Uninterruptible Power System
1 — 14
Introduction
Содержание Comet 100 kVA
Страница 1: ...COMET 40 150 kVA Uninterruptible Power System Installation and User s Manual...
Страница 10: ...this page left blank intentionally x 86 160310 00 Comet 40 150 kVA Uninterruptible Power System...
Страница 28: ...this page left blank intentionally 1 18 Introduction 86 160310 00 Comet 40 150 kVA Uninterruptible Power System...
Страница 35: ...Figure UPS input output connections 100 150kVA 2 3 86 160310 00 2 7 Installation Installation and Users Manual...
Страница 36: ...This page left blank intentionally 2 8 Installation 86 160310 00 Comet 40 150 kVA Uninterruptible Power System...
Страница 62: ...this page left blank intentionally 86 160310 00 Comet 40 150 kVA Uninterruptible Power System...
Страница 64: ......
Страница 65: ......
Страница 66: ...Nothing will stop you now 1660 Scenic Avenue Costa Mesa California 92626 714 557 1636 www mgeups com...