6 – Door Control AS 210 B / Rev.A 2.0
Detailed circuit diagram for mains connection and
motor 230 V / 3-phase
Description:
F1
Thermal fuse, control voltage
F2
Thermal overload protection for motor
K1
Protection OPEN
K2
Protection CLOSE
M
Motor (230 V / 50 Hz / 3-phase)
S3
Safety limit switch OPEN
(normally closed contact)
S4
Safety limit switch CLOSE
(normally closed contact)
S7
Safety switch, emergency manual operation (normally
closed contact)
T1 Transformer
X1
Terminal block for mains connection
X2
Terminal block for motor
X4
Terminal block for mains voltage selection
Detailed circuit diagram for mains connection and
motor 230 V / single phase
Description:
F1
Thermal fuse, control voltage
F2
Thermal overload protection for motor
K1
Protection OPEN
K2
Protection CLOSE
M
Motor (230 V / 50 Hz)
S3
Safety limit switch OPEN (normally closed contact)
S4
Safety limit switch CLOSE (normally closed contact)
S7
Safety switch, emergency manual operation (normally
closed contact)
T1 Transformer
X1
Terminal block for mains connection
X2
Terminal block for motor
X4
Terminal block for mains voltage selection
Connection:
Connect the controls to the mains power supply.
Connect the controls to the motor.
Cable groups must be fixed close to their relevant terminals
using a cable tie.
Initial operation
5
4W
VU
L3
L2
L1
PE
1
2
3
230V
230 V / 50 Hz
5
4N
AUF
ZU
LN
PE
1 2
3
230V
230 V / 50 Hz