Models: LMFP- (48 / 60 / 72 / 84 / 96 / 108 / 120)

B-Vent* Gas Appliance with Masonry Firebox

Do not store or use gasoline or other 

flammable vapors and liquids in the 

vicinity of this or any other appliance.

WHAT TO DO IF YOU SMELL GAS:

• 

Do not try to light any appliance.

• 

Do not touch any electrical switch; do 

not use any phone in your building.

• 

Immediately call your gas supplier from 

a neighbor’s phone and follow the gas 

supplier’s instructions.

• 

If you cannot reach your gas supplier, 

call the fire department.

Installation and service must be 

performed by a qualified installer, service 

agency, or the gas supplier.

WARNING:

If the information in these instructions is 

not followed exactly, a fire or explosion 

may result causing property damage, 

personal injury or death.

The logs and burner must be permanently installed and 

are only for use in this appliance. This appliance must be 

connected to a working flue meeting the requirements of 

the ANSI Z21.50 standard.

Solid-fuels shall not be burned in this appliance.

This appliance must be vented vertically through the 

roof. This appliance is not for installation in manufactured 

or mobile homes. The installation, including provisions 

for  combustion,  ventilation  air,  and  required  minimum 

permanent vent opening, must conform with the National 

Fuel Gas Code (ANSI Z223.1/NFPA 54) and applicable 

local building codes. 

This gas appliance is designed to 

burn with yellow flames; thus adequate ventilation is 

absolutely necessary.

IMPORTANT:

 READ THESE INSTRUCTIONS

CAREFULLY BEFORE STARTING

INSTALLATION OF THIS APPLIANCE. 

WARNING:

This gas appliance must not be connected to a chimney 

fuel servicing a solid fuel burning appliance.

Do not store gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.

INSTALLER

:

 Leave this manual with the appliance.

CONSUMER:

 Retain this manual for future reference.

This appliance is only for use with the type of gas indicated on 

the rating plate. This appliance is not convertible for use with 

other gases, unless a certified kit is used.

REV 010721

*Class A chimney can be used as an optional chimney system. Consult chimney system manufacturer’s instructions.

Inc.

PFS

®

US

C

Содержание Mason-Lite LMFP-108

Страница 1: ...I Z21 50 standard Solid fuels shall not be burned in this appliance This appliance must be vented vertically through the roof This appliance is not for installation in manufactured or mobile homes The...

Страница 2: ...Pg 20 Mason Lite Firebrick Liners Pg 21 Appliance Finishes and Combustible Trim Clearances Pg 21 Installing Outside Air Pg 21 Mason Lite Chimney Systems Pg 22 23 Venting Installation Pg 24 Chimney Ter...

Страница 3: ...uctions Note Certain installation conditions may require an Enervex Exhausto Termination System including ADC100 Controller Consult Manual Chimney Heights Horizontal vent runs are approved for up to 7...

Страница 4: ...4 LMFP 48 60 72 84 Appliance Parts Diagram LMFP 48 60 72 84 Appliance Parts Diagram Figure 2 14 19 18 16 15 12 13 7 8 6 5 2 3 1 4 9 10 17 20 11 IT...

Страница 5: ...T HOLE 1 4 SIDE WALL 5 5 REAR WALL SML SEC 3 6 REAR WALL 3 7 5 x 3 x 61 x 25 ANGLE IRON NOT SUPPLIED SOURCE LOCALLY 1 8 LOWER DOME FRONT 2 9 LINTEL 2 10 SMOKE SHELF 1 11 SPILL SWITCH 1 12 LOWER SIDE D...

Страница 6: ...17 16 17 8 9 17 18 8 9 11 13 14 12 13 11 15 20 21 5 6 4 3 7 5 5 1 2 2 1 5 7 6 6 10 23 24 5 4 22 Figure 1 WARNING Failure to position the parts in accordance with these diagrams or failure to use only...

Страница 7: ...ER DOME FRONT CENTER 1 13 LINTEL 2 14 LINTEL CENTER 1 15 4X3 ANGLE IRON NOT SUPPLIED SOURCE LOCALLY 1 16 UPPER DOME SIDE 2 17 UPPER DOME 4 18 UPPER DOME CENTER 2 19 DOME TOP 2 20 SPILL SWITCH CHANNEL...

Страница 8: ...stand each phase completely before going on to subsequent instructions Attention All the illustrations in this manual are for general reference only Do not scale drawings Actual design elements will v...

Страница 9: ...xamples of multiple configurations Please consult with local Structural Engineer for suspension and support calculations 4 Sided option Left Side option Peninsula option Right Side option See Thru opt...

Страница 10: ...e The burner specified for use with this gas appliance is non convertible and only meant to be used with the gas listed on the rating plate GUIDELINES FOR USE All current and future users of Mason Lit...

Страница 11: ...RAMING NON COMBUS H2 SPILL SWITCH CHANNEL Appliance Framing Dimensions Non Combustible Floor Systems Figure 6 WARNING Failure to position the parts in accordance with these diagrams or failure to use...

Страница 12: ...k Lining Attention Any gaps between the appliance front and fascia material should be sealed with non combustible epoxy PLAN 2 2 2 8 MIN 2 MIN MIN PLAN MIN MIN 113 2 MIN 8 NON COMBUSTIBLE FACING MATER...

Страница 13: ...ance Overall Dimensions LMFP 120 Figure 8a LMFP 120 Appliance Overall Dimensions ALL DIMENSIONS ARE IN INCHES ALL DIMENSIONS ARE MINIMUM MORTAR THICKNESS MAY ADD A TOTAL OF UP TO 1 INCH TO THE OVERALL...

Страница 14: ...remain hot for a time afterward Allow the surface to cool before touching it Carefully supervise young children when they are in the room with the appliance All appliance openings for both combustion...

Страница 15: ...e addition of floor joists to align with the anchor brackets allows the brackets to be directly connected to the floor joists Note that additional floor joists may be required to support the weight of...

Страница 16: ...I 240 1 For wood structural members having a moisture content of less than 16 per cent at time of installation and used under dry conditions the deflection resulting from L 0 5D is permitted to be sub...

Страница 17: ...bar x 36 long included with unit Eight 8 ea All thread x 12 long with nuts and washers ALL UNITS Three 3 90 lb bags of ready mix concrete with 1 4 or smaller aggregate 6 Structural Metal Base to allow...

Страница 18: ...h dimension allows for an approximate gap of 1 8 between slabs for the additional mortar to unite the remaining slabs Continue process for remaining hearth sections while moistening and adding mortar...

Страница 19: ...he last tier of side walls are installed place 3 rebar 3 ft long pieces vertically through the cells into the holes in the hearth adjacent to the rebar and or all thread sticking up from the hearth an...

Страница 20: ...s are smooth and uniform Make sure connections are covered with an adequate amount of mortar Remember that you have the option of using shims but they must be removed and any holes filled Make any adj...

Страница 21: ...E SHEATHING ZONE 2 2 2 NON COMBUSTIBLE ONLY ZONE Figure 30 Mantel clearances 2 Walls That Adjoin Safety codes and all practical outlooks insist that your appliance cannot be installed closer than 2 ft...

Страница 22: ...fts caused by faulty mechanical systems adverse weather conditions or any other inclement environmental situations over which the manufacturer has no control 5 Inspect all appliance chimney components...

Страница 23: ...l be required for the installation Bear in mind that the minimum height of the Mason Lite once installed is 14 0 fourteen feet and that it is higher if offsets are used Here is how to calculate the he...

Страница 24: ...only through the outer chimney For systems needing multiple offsets with sections over 4 four feet please use an Enervex Fan to ensure a good positive draft Venting Installation Venting Installation...

Страница 25: ...be painted in order to protect it them from rusting and weathering Particularly if you are installing the appliance and chimney near water or in a high humidity area the manufacturer recommends a top...

Страница 26: ...ay be necessary Nominal BTU based on gas inlet pressure Nominal gas inlet pressure for natural gas is 5 W C Installing the valve control box assembly 1 Fasten the valve control box assembly to a stud...

Страница 27: ...l be able to run the burner for as long as you like Attaching the Burner and the Grate 1 Unpack the burner assembly and place the rear legs of the burner into the brackets in the back of the firebox 2...

Страница 28: ...as far forward as possible while keeping the back parallel with the burner pipe Figure 41 3 Place top logs across the front and back logs in the order and positions shown in Figure 44 WARNING Failure...

Страница 29: ...URES DRAWN MODEL CHECK QA THIS DOCUMENT AUTHENTICATED WITH DIGITAL SIGNATURES MENT CONTAINS CONFIDENTIAL INFORMATION AND MAY NOT BE REPRODUCED OR DISCLOSED TO OTHERS WITHOUT WRITTEN AUTHORIZATION FROM...

Страница 30: ...30 LOG SET 120 Figure 49...

Страница 31: ...ease and all flames main burner and pilot will go out see important note below OPERATING THE BURNER USING THE REMOTE Move the wall switch to the REMOTE position and follow the instructions included in...

Страница 32: ...valve is installed on either the gas in or gas out side of the valve It is recommended to hard pipe in the connec ons with unions installed inside the box PILOT INSTALLATION Un coil the pilot tubing t...

Страница 33: ...it is impera ve that you follow the steps outlined below to ensure proper and safe opera on If you encounter any irregulari es refer to the TROUBLESHOOTING GUIDE 1 Check all wiring connec ons 2 Turn o...

Страница 34: ...Pilot generator may not be producing sufficient millivolts a Check with a millivolt meter Should be 250 millivolts or more b Pilot flame making a blowing sound b Pilot needs adjusting see Checking an...

Страница 35: ...slab The concrete strength and durability shall comply with Sections 1903 1904 and 1905 of the International Building Code IBC TABLE R402 2 MINIMUM SPECIFIED COMPRESSIVE STRENGTH OF CONCRETE MINIMUM...

Страница 36: ...ly b Lines defining areas are approximate only Local conditions may be more or less severe than indicated by region classification A severe classification is where weather conditions result in signifi...

Страница 37: ...been installed or to the persons or property therein arising out of the use misuse or installation of properly manufactured Masonry Fireplace Industries products The appliance must be used in accordan...