MI 2883 Energy Master
Operating the instrument
86
Table 3.75: Keys in Connection setup menu
Selects Connection setup parameter to be modified.
Changes selected parameter value.
Enters into submenu.
Confirms Factory reset.
Returns
to the “MEASUREMENT SETUP” submenu.
3.19.2
Event setup
In this menu user can setup voltage events and their parameters. See 5.1.11 for further
details regarding measurement methods. Captured events can be observed through
EVENTS TABLE screen. See 3.15 and 5.1.11 for details.
Figure 3.59: Event setup screen
Table 3.76: Description of Event setup
Nominal voltage
Indication of type (L-N or L-L) and value of nominal voltage.
Swell Threshold
Set swell threshold value in % of nominal voltage.
Swell Hysteresis
Set swell hysteresis value in % of nominal voltage.
Dip Threshold
Set dip threshold value in % of nominal voltage.
Dip Hysteresis
Set dip hysteresis value in in % of nominal voltage.
Interrupt Threshold
Set interrupt threshold value in % of nominal voltage.
Interrupt Hysteresis
Set interrupt hysteresis in % of nominal voltage.
Table 3.77: Keys in Event setup screen
HELP
Shows help screens for Dip, Swell and Interrupt. See
5.1.12 for details.
ENTER
F2