MI 2883 Energy Master
Operating the instrument
67
Table 3.55: Keys in General recorder setup screen
START
STOP
Starts the recorder.
Stops the recorder.
CONFIG
Shortcut to Connection setup. See 4.2 for details.
CHECK C.
Check connection settings. See 3.19.1 for details.
Enters recorder starting date/time setup.
Keys in Set start time window:
Selects parameter to be changed.
Modifies parameter.
Confirms selected option.
Exits Set start time window without modifications.
Selects parameter to be changed.
Modifies parameter.
Returns to the “RECORDERS” submenu.
3.15 Events table
In this table captured voltage dips, swells and interrupts are shown. Note that events
appear in the table after finishing, when voltage return to the normal value. All events
can be grouped according to IEC 61000-4-30. Additionally for troubleshooting purposes
events can be separated by phase. This is toggled by pressing function key F1.
Group view
In this view voltage event are grouped according to IEC 61000-4-30 (see section 5.1.11
for details). Table where events are summarized is shown below. Each line in table
represents one event, described by event number, event start time, duration and level.
Additionally in colon “T” event characteristics (Type) is shown (see table below for
details).
F1
F3
F4
ENTER
ENTER