temperature and unnecessary actuator movement. The proper values 
is  set  experimentally.  It  is  recommended  to  set  this  parameter  in  the 
range of 2-6 [3]. 

Constant for integration time 

The  greater  the  value  of  this  parameter,  the  slower  is  the  actuator 
reaction  for  temperature  deviation.  Setting  too  lower  values  can  lead 
to  unnecessary  actuator  movements,  too  high  value  extending  the 
time  needed  to  find  set  value  of  the  temperature.  The  right  value  is 
being  edited  according  to  research  results.  It  is  recommended  to  set 
this parameter value between 100 and 180 [160]. 

Pump shut-off from thermostat 

Setting  this  parameter  to  “YES”  results  in  closing  the  mixer  and 
deactivating  the  mixer  pump  after  opening  the  room  thermostat 
contact (the room is warm). This setting is not recommended because 
the heated room may cool down too much. 

Mixer insensitivity* 

This  parameter  determines  the  value  of  temperature  insensitivity 
(dead  zone)  of  the  mixer  control  system.  The  regulator  controls  the 
mixer so that the measured temperature in the mixer circuit  sensor is 
equal  to  the  set  temperature.  In  order  to  avoid  frequent  actuator 
movements  which  can  wear  it  down  unnecessarily,  the  parameter 
should only be regulated when the measured temperature of the mixer 
circuit  is  lower  or  higher  than  the  set  temperature  by  a  value 
exceeding the 

mixer insensitivity

15.6

 

 H OUTPUT 

 

H output 

H1 output 

There are option to choose from: 
Reserve boiler 

– 46-47 output controls the reserve boiler, 

Alarms 

– when an alarm occurs, output 46-47 is being activated, 

H2 output* 

Functions analogous to terminal H1 executed in terminal 30-31 of the 
B module 

Reserve boiler** 

This option appears, when an H1 output = reserve boiler,  defines the 
temperature of solid fuel boilers above which the reserve boiler will be 
turn  on  or  off.  During  buffer  operation  it  also  defines  the  buffer 
temperature above which the reserve boiler will be turn on or off. 

15.7

 

 ADVANCED SETUP 

Show advanced setup 

Available options: 

 

YES (shows hidden parameters, which edition is not 
recommended) 

 

NO (hides hidden parameters) 

 

15.8

 

 RESTORE DEFAULT SETTINGS 

 

Restore default settings 

Restoring the service settings will automatically lead to restoring the 
settings from main menu (user settings) 

Содержание ecoMAX860P2-T

Страница 1: ...C SOLID FUEL FIRED BOILERS WITH INGITION GUTTER AND RETORT FEEDERS INSTALLATION AND OPERATING MANUAL ISSUE 1 0 APPLIES TO SOFTWARE MODULE A B PANEL v06 XX XX v06 XX XX 11 2015 functions available in t...

Страница 2: ...2...

Страница 3: ...VERHEATING STB LIMITER OPEN 18 9 10 MAX EXHAUST TEMPERATURE EXCEEDED SENSOR DAMAGE DANGER 18 9 11 LACK OF COMMUNICATION 18 9 12 UNSUCCESSFUL ATTEMPT OF BUFFER LOADING 18 9 13 FAN OR FAN SPEED SENSOR F...

Страница 4: ...flame going back to the fuel feeder etc The regulator is intended for boiler manufacturers Before applying the regulator a boiler manufacturer should check if the regulator s mating with the given boi...

Страница 5: ...to two parts for user and fitter Yet both parts contain important information significant for safety issues hence the user should read both parts of the manual We are not responsible for any damages c...

Страница 6: ......

Страница 7: ...REGULATOR INSTRUCTION MANUAL ecoMAX860P2 T...

Страница 8: ...Night time decrease boiler On No Yes Reduction value Schedule HUW settings HUW preset temperature HUW pump mode Off Priority No priority HUW container hysteresis HUW disinfection Night time decrease...

Страница 9: ...been reached of preset boiler temperature for active time intervals increase of preset boiler temperature for the time of HUW container filling increase of preset boiler temperature by mixer circuit i...

Страница 10: ...lted Boiler operation cannot be continued automatically service crew must intervene After removing causes of impossibility to fire up the boiler must be restarted 8 5 OPERATION The fan operates contin...

Страница 11: ...ime expires the regulator switches to EXTINGUISHING mode unless the boiler temperature decreases and the boiler automatically switches to OPERATION mode For the setting Supervision time 0 the regulato...

Страница 12: ...ght time decrease and Service Settings CH and HUW settings The time settings of the circulation pump are analogous to the settings of night time decrease The pump will be off in the defined time perio...

Страница 13: ...e heating cycle temperature by a constant value when the preset room temperature is reached Analogously as specified in the previous point not recommended or automatically continuously correct the hea...

Страница 14: ...have good thermal insulation the heating curve can have lower value The regulator can increase or decrease the preset temperature calculated in accordance with the heating curve if it exceeds the tem...

Страница 15: ...selected and confirmed YES fuel level is set to 100 Note Fuel may be replenished at any time without a need to wait for complete empty fuel tank Replenish fuel always to the level corresponding to 100...

Страница 16: ...tom of the screen there is a button Upon activation of this key a quick selection menu appears To add new item to this menu hold respective icon pressed in pie menu for a while To remove selected item...

Страница 17: ...er control is taken over by the emergency system and the boiler continues to operate Note operating in emergency mode is allowed only under user supervision and until the arrival of the service team t...

Страница 18: ...igital communication link In case a cable of this link will be damaged an alarm will occur on the screen with the information Attention No communication The controller doesn t stop to operate and work...

Страница 19: ...19 CONTROLLER INSTALLATION AND SERVICE SETTINGS MANUAL ecoMAX860P2 T...

Страница 20: ...rature set a high set temperature of the boiler In order to improve the water circulation in natural systems highlighted circuit in the figure use large nominal diameter pipes and four way valve avoid...

Страница 21: ...ctivation temperature 55 C Menu service settings CH and HUW settings CH pump boiler pump YES Menu service settings CH and HUW settings Mixer 1 control CH activated Menu service settings Mixer 1 contro...

Страница 22: ...ice settings buffer settings Buffer load activation temperature 50 Menu service settings buffer settings Buffer load deactivation temperature 75 Menu service settings buffer settings Mixer 1 control C...

Страница 23: ...vibrations greater than those typical of normal road transport 13 REGULATOR INSTALLATION 13 1 Environmental conditions Due to the risk of fire is prohibited to use the controller in explosive gas and...

Страница 24: ...In such case the user has access to the face plate of the executive module The cover may be composed from boiler elements surrounding the whole module The module cover does not provide resistance to...

Страница 25: ...in accordance with this drawing the device has protection rate IP 20 from the front side of the executive module enclosure specified on the rating plate From the side of the terminals the casing has p...

Страница 26: ...ation with low voltage devices below 12 V Connecting mains supply 230V to terminals 22 49 and to transmission connectors RS485 will damage the regulator and creates risk of an electric shock Tips of t...

Страница 27: ...1 temperature sensor M2 CT4 regulated circuit mixer 2 temperature sensor WS CT6 P weather sensor FT CT2S exhaust temperature sensor BP control panel B additional heating circuits control module lambd...

Страница 28: ...RM4 mixer 4 room thermostat FS fuel level sensor used with the BU feeder H2 voltage output for controlling the auxiliary boiler or alarm signalling or hot usable water circulation pump RELAY relay L N...

Страница 29: ...t to the temperature not exceeding 100 C 13 9 Connecting weather sensor The regulator cooperates only with a weather sensor of the CT6 P type The sensor should be installed on the coldest wall of the...

Страница 30: ...s Boiler Settings Pump off by therm 13 13 Connection of reserve boiler The regulator can control a reserve boiler gas or oil fired eliminating the necessity of enabling or disabling this boiler manual...

Страница 31: ...f boiler water is limited You are advised to get familiar with the position of the valve corresponding to its maximum opening before commencement of work so that you may ensure heat collection from th...

Страница 32: ...ck whether the valve is properly connected 13 16 Connecting temperature limiter STB In order to prevent the boiler from overheating due to the regulator malfunction an STB safety temperature limiter o...

Страница 33: ...ion method exhaust only water and exhaust Exhaust temperature fan reduction Return protection 4 way return protection Return hysteresis Min return temperature Valve closing Min boiler temperature Max...

Страница 34: ...dditional module is connected or the parameter is hidden Manufacturer menu Reset counters Reset alarms Exhaust alarm temperature Flame return feed time Flame return detection delay Flame return alarm...

Страница 35: ...n OPERATION mode cycle time Complete cycle time of fuel feeding in OPERATION mode OPERATION cycle time OPERATION feed time feeder standstill time Feeder efficiency Efficiency of the fuel feeder in kg...

Страница 36: ...mum feeder temperature is displayed When this temperature is exceeded the feeder is engaged for a predefined time with a several minute pause If the temperature drops the regulator resumes normal oper...

Страница 37: ...es on the hot usable water pump and opens the mixer circuits in order to cool the boiler down The regulator will turn the hot usable water pump when the temperature of this water exceeds the maximum v...

Страница 38: ...oiler is on a satisfactory level the regulator will not change it in order to load the HUW tank buffer or mixer circuit The increase of the set boiler temperature for the period of loading the HUW tan...

Страница 39: ...uator Thermostat select Options to choose from Shut down it cuts the influence of room thermostat upon the boiler operation Universal it turns on the no nc room thermostat coupled to 42 43 contacts it...

Страница 40: ...emperature in the mixer circuit sensor is equal to the set temperature In order to avoid frequent actuator movements which can wear it down unnecessarily the parameter should only be regulated when th...

Страница 41: ...ecoTOUCH control panel from the regulator housing Insert memory card into indicated slot Memory card should contain new software stored in the pfc format two files one with software for control panel...

Страница 42: ...should be connected also when in the boiler is not in use This function can be enabled also when the regulator is turned off via keyboard regulator in STAND BY 17 4 Bunker feeder After connecting an a...

Страница 43: ......

Страница 44: ......

Страница 45: ......

Страница 46: ......

Страница 47: ......

Страница 48: ...Jacek Kucharewicz ul Sikorskiego 66 16 100 Sok ka Poland tel 48 85 711 94 54 www metalfachtg com pl...

Отзывы: