temperature and unnecessary actuator movement. The proper values
is set experimentally. It is recommended to set this parameter in the
range of 2-6 [3].
Constant for integration time
The greater the value of this parameter, the slower is the actuator
reaction for temperature deviation. Setting too lower values can lead
to unnecessary actuator movements, too high value extending the
time needed to find set value of the temperature. The right value is
being edited according to research results. It is recommended to set
this parameter value between 100 and 180 [160].
Pump shut-off from thermostat
Setting this parameter to “YES” results in closing the mixer and
deactivating the mixer pump after opening the room thermostat
contact (the room is warm). This setting is not recommended because
the heated room may cool down too much.
Mixer insensitivity*
This parameter determines the value of temperature insensitivity
(dead zone) of the mixer control system. The regulator controls the
mixer so that the measured temperature in the mixer circuit sensor is
equal to the set temperature. In order to avoid frequent actuator
movements which can wear it down unnecessarily, the parameter
should only be regulated when the measured temperature of the mixer
circuit is lower or higher than the set temperature by a value
exceeding the
mixer insensitivity
.
15.6
H OUTPUT
H output
H1 output
There are option to choose from:
Reserve boiler
– 46-47 output controls the reserve boiler,
Alarms
– when an alarm occurs, output 46-47 is being activated,
H2 output*
Functions analogous to terminal H1 executed in terminal 30-31 of the
B module
Reserve boiler**
This option appears, when an H1 output = reserve boiler, defines the
temperature of solid fuel boilers above which the reserve boiler will be
turn on or off. During buffer operation it also defines the buffer
temperature above which the reserve boiler will be turn on or off.
15.7
ADVANCED SETUP
Show advanced setup
Available options:
YES (shows hidden parameters, which edition is not
recommended)
NO (hides hidden parameters)
15.8
RESTORE DEFAULT SETTINGS
Restore default settings
Restoring the service settings will automatically lead to restoring the
settings from main menu (user settings)
Содержание ecoMAX860P2-T
Страница 2: ...2...
Страница 6: ......
Страница 7: ...REGULATOR INSTRUCTION MANUAL ecoMAX860P2 T...
Страница 19: ...19 CONTROLLER INSTALLATION AND SERVICE SETTINGS MANUAL ecoMAX860P2 T...
Страница 43: ......
Страница 44: ......
Страница 45: ......
Страница 46: ......
Страница 47: ......
Страница 48: ...Jacek Kucharewicz ul Sikorskiego 66 16 100 Sok ka Poland tel 48 85 711 94 54 www metalfachtg com pl...